| choice | Choice specifies an exclusive marker selection | 
|---|---|
| ahuZoneDelivery | AHU delivery method of conditioned air to the zone | 
| chilledBeamZone | AHU supplies air to chilled beam terminal units | 
| directZone | AHU supplies air directly to the zone | 
| multiZone | AHU discharge air is split into a duct per zone | 
| vavZone | AHU supplies air to VAV terminal units | 
| airVolumeAdjustability | Ability of air handling equip to adjust volume of air flow | 
| constantAirVolume | Delivers a constant volume of air flow | 
| variableAirVolume | Delivers a variable volume of air flow | 
| atesDesign | Design type of the ATES underground system | 
| atesClosedLoop | The ATES uses closed piping to transport a water/glycol mixture through the ground | 
| atesDoublet | The ATES has one or more pairs of a separate warm and cool well | 
| atesDoubletPaired | The ATES is as a doublet, but with specific warm and cool wells linked together | 
| atesMono | The ATES has only one physical well | 
| atesUnidirectional | Similar to a doublet, but water always flows in the same direction from the extraction to the infiltration well | 
| chillerMechanism | Primary mechanism of chiller | 
| chiller-absorption | Cooling process using energy from heat source such as hot water | 
| chiller-centrifugal | Compression via a continuous flow of fluid through an impeller | 
| chiller-reciprocal | Piston compressor driven by a crankshaft | 
| chiller-rotaryScrew | Rotary screw compression | 
| condenserLoop | Open or closed loop for condenser working fluid | 
| condenserClosedLoop | Working fluid is kept separate from fluid used for heat transfer into the atmosphere | 
| condenserOpenLoop | Uses working fluid itself for evaporation into the atmosphere | 
| coolingProcess | Processed used to cool a substance | 
| airCooling | Cooling by dissipating heat into the surrounding air | 
| chilledWaterCooling | Cooling using transfer of heat to chilled water | 
| condenserCooling | Removal of heat through the process of water condensation | 
| dxCooling | Cooling using direct expansion of a refrigerant vapor | 
| waterCooling | Cooling using transfer of heat to water which is not explicitly chilled | 
| ductConfig | Ductwork configuration | 
| dualDuct | Two ducts | 
| singleDuct | One single duct | 
| tripleDuct | Three ducts | 
| ductDeck | Cold, hot, or neutral deck | 
| coldDeck | Duct carries air for cooling | 
| hotDeck | Duct carries air for heating | 
| neutralDeck | Duct carries air which by-passes both heating and cooling coils | 
| ductSection | Equipment section of ductwork | 
| discharge | Duct for air leaving an equipment | 
| economizer | Duct to access fresh outside air only for economizing, not ventilation | 
| exhaust | Duct used to expel air back outside | 
| flue | Duct for exhausting combustion | 
| inlet | Duct with air entering an equipment | 
| mixed | Duct where fresh outside air and return air is mixed together | 
| outside | Duct to access fresh outside air for both ventilation and economizer | 
| return | Duct returning air back to equipment | 
| ventilation | Duct to access fresh outside air only for ventilation, not economizing | 
| heatingProcess | Processed used to heat a substance | 
| biomassHeating | Heating by the combustion of biomass | 
| coalHeating | Heating by the combustion of coal | 
| dxHeating | Heating using direct expansion of a refrigerant vapor | 
| elecHeating | Heating by the conversion of electrical energy | 
| fuelOilHeating | Heating by the combustion of fuel oil | 
| hotWaterHeating | Heating using energy of hot water | 
| naturalGasHeating | Heating by the combustion of natural gas | 
| propaneHeating | Heating by the combustion of propane | 
| steamHeating | Heating using energy of steam | 
| meterScope | Classifies a meter as a main site meter or submeter | 
| siteMeter | Main meter for the associated site | 
| submeter | Submeters measure usage of a sub-system or equipment within a site | 
| pfScope | Power factor scope | 
| pfDisplacement | Displacement power factor, which accounts for the phase angle between voltage and current but excludes effects of nonlinear waveforms ( harmonic distortion) | 
| pfDistortion | Distortion power factor, which measures the component of power factor attributable to harmonic distortion in voltage and current waveforms | 
| pfTrue | True power factor, which includes effects of harmonic distortion | 
| pfStandard | Standard for interpreting power factor's positive or negative sign | 
| pfIec | Power factor according to the IEC convention defines a positive or negative sign based on the direction of active power flow | 
| pfIeee | Power factor according to the IEEE convention defines a positive or negative sign based on whether the load is capacitive or inductive | 
| phaseCount | Number of phases for an AC electrical power system or connected equipment | 
| singlePhase | Single-phase AC electricity | 
| splitPhase | Split-phase AC electricity | 
| threePhase | Three-phase AC electricity | 
| twoPhase | Two-phase AC electricity | 
| pipeFluid | Type of fluid conveyed by piping | 
| pipeSection | Equipment section of piping | 
| bypass | Pipe used to bypass an equipment | 
| circ | Pipe used to circulate fluid through an equipment or system | 
| entering | Pipe conveys fluid into an equipment | 
| header | Pipe used as central connection or manifold for other piping runs | 
| leaving | Pipe conveys fluid out of an equipment | 
| plantLoop | Plant piping loop | 
| primaryLoop | Pipework which circulates closest to the energy source | 
| secondaryLoop | Pipework which circulates closest to the building or end use | 
| tertiaryLoop | Pipework which circulates within the building | 
| pointFunction | Classifies the point as a sensor, command, or setpoint | 
| cmd | Point is a command, actuator, AO/BO | 
| sensor | Point is a sensor, input, AI/BI | 
| sp | Point is a setpoint, soft point, internal control variable, schedule | 
| synthetic | Synthetic point with computed operational data | 
| computed | Computed point | 
| ml | Machine learning point | 
| sim | Simulation point | 
| pointQuantity | Quantity the point senses or controls | 
| pointSubject | What the point senses or controls | 
| simScenario | See Synthetics chapter | 
| simBaseline | See Synthetics chapter | 
| simOperation | See Synthetics chapter | 
| simOptimum | See Synthetics chapter | 
| tankSubstance | Substance stored by a tank | 
| vavAirCircuit | How does the VAV pull in air | 
| vav-parallel | VAV pulls air from outside the primary air flow | 
| vav-series | VAV pulls air from the primary air flow | 
| vavModulation | How does VAV modulate the temp based on duct pressure | 
| pressureDependent | VAV damper modulates to control space temp | 
| pressureIndependent | VAV damper or a control valve that modulates to maintain desired flow setpoint |