VAVs
Overview
The vav tag is used to model variable air volume assets. VAVs should always be marked as equip.
Tags
VAVs should be classified with the following type tags:
coolOnlyseriesfanPoweredelecReheatseriesfanPoweredhotWaterReheatparallelfanPoweredelecReheatparallelfanPoweredhotWaterReheat
The additional equip level tags are defined for VAVs:
hvac: always specified to mark as an HVAC assetsingleDuctordualDuct: ductwork configurationahuRef: supply AHUchilledWaterPlantRef: plant supplying chilled water if applicablepressureDependentorpressureIndependent: control based on duct static pressurehotWaterPlantRef: reference plant supplying hot watersteamPlantRef: reference plant supplying steam
Sections
We associate points with sections of a VAV using these tags:
entering: air entering the unit from the AHUdischarge: air exiting the unit to be supplied to the zoneszone: conditioned space associated with the unit
However since most points are not clearly associated with the entering or discharge section we omit a section tag for most points. However any points which would conflict with the zone points however must be qualified with either discharge or entering tags.
Points
VAVs points include zone points:
zoneairtempsensorzoneairtempeffectivespzoneairtempocccoolingspzoneairtempoccheatingspzoneairtempunocccoolingspzoneairtempunoccheatingspzoneairtempstandbycoolingspzoneairtempstandbyheatingspzoneairhumiditysensorzoneairco2sensorzoneairco2sp
Other standardized points: