id:@a-0000 dis:Alpha area:151455ft² geoAddr:"123 Prarie St, Hugo, CO 80821" geoCity:Hugo geoCoord:C(39.04532,-103.57159) geoCountry:US geoElevation:2956m geoPostalCode:"80821" geoState:CO geoStreet:"123 Prarie St" site tz:Denver weatherStationRef:@a-07eb --- id:@a-0001 dis:Alpha Airside AHU-2 ahu chilledWaterCooling chilledWaterRef:@a-07b8 elec equip hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 vavZone --- id:@a-0002 dis:Alpha Airside AHU-2 Chilled Water Valve chilled cmd cool cur custom:{description:"Clg_Valve_Cmd"} equipRef:@a-0001 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0003 dis:Alpha Airside AHU-2 Discharge Fan Speed air cmd cur custom:{description:"SF VFD Signal" supply} discharge equipRef:@a-0001 fan his kind:Number point siteRef:@a-0000 speed tz:Denver unit:"%" --- id:@a-0004 dis:Alpha Airside AHU-2 Hot Water Valve cmd cur custom:{description:"Htg_Valve_Cmd"} equipRef:@a-0001 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0005 dis:Alpha Airside AHU-2 Mixed Air Temp air cur custom:{description:"MAT"} equipRef:@a-0001 his kind:Number mixed point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0006 dis:Alpha Airside AHU-2 Outside Air Damper air cmd cur custom:{description:"Econ_Cmd"} damper equipRef:@a-0001 his kind:Number outside point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0007 dis:Alpha Airside AHU-2 Outside Air Enthalpy air cur custom:{description:"Enthalpy" enthalpy} equipRef:@a-0001 his kind:Number outside point sensor siteRef:@a-0000 tz:Denver unit:"BTU/lb" --- id:@a-0008 dis:Alpha Airside AHU-2 Outside Air Temp air cur custom:{dryBulb description:"OAT"} equipRef:@a-0001 his kind:Number outside point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0009 dis:Alpha Airside AHU-2 RF VFD airRef:@a-0001 elec equip equipRef:@a-0001 fan hvac meter return siteRef:@a-0000 --- id:@a-000a dis:Alpha Airside AHU-2 RF VFD Return Fan Frequency air cur equipRef:@a-0009 fan freq his kind:Number point return sensor siteRef:@a-0000 tz:Denver unit:Hz --- id:@a-000b dis:Alpha Airside AHU-2 RF VFD Return Fan Power air cur elec equipRef:@a-0009 fan his kind:Number point power return sensor siteRef:@a-0000 tz:Denver unit:kW --- id:@a-000c dis:Alpha Airside AHU-2 RF VFD Return Fan Status air cur equipRef:@a-0009 fan his hisMode:cov kind:Bool point return run sensor siteRef:@a-0000 tz:Denver --- id:@a-000d dis:Alpha Airside AHU-2 Relief Air Damper air cmd cur custom:{description:"Relief Damper Signal"} damper equipRef:@a-0001 exhaust his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-000e dis:Alpha Airside AHU-2 Return Air Damper air cmd cur custom:{description:"Econ_Cmd"} damper equipRef:@a-0001 his kind:Number point return siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-000f dis:"Alpha Airside AHU-2 Return Air Fan S/S Command" air cmd cur custom:{description:"RF VFD S/S"} equipRef:@a-0001 fan his hisMode:cov kind:Bool point return run siteRef:@a-0000 tz:Denver --- id:@a-0010 dis:Alpha Airside AHU-2 Return Air Temp air cur custom:{description:"RAT"} equipRef:@a-0001 his kind:Number point return sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0011 dis:Alpha Airside AHU-2 Return Fan Speed air cmd cur custom:{description:"RF VFD Speed"} equipRef:@a-0001 fan his kind:Number point return siteRef:@a-0000 speed tz:Denver unit:"%" --- id:@a-0012 dis:Alpha Airside AHU-2 Return Fan Status air cur custom:{description:"RF Status"} equipRef:@a-0001 fan his hisMode:cov kind:Bool point return run sensor siteRef:@a-0000 tz:Denver --- id:@a-0013 dis:Alpha Airside AHU-2 SF VFD airRef:@a-0001 discharge elec equip equipRef:@a-0001 fan hvac meter siteRef:@a-0000 --- id:@a-0014 dis:Alpha Airside AHU-2 SF VFD Discharge Fan Power-1 air cur custom:{supply} discharge elec equipRef:@a-0013 fan his kind:Number point power sensor siteRef:@a-0000 tz:Denver unit:kW --- id:@a-0015 dis:Alpha Airside AHU-2 SF VFD Supply Fan Frequency air cur custom:{supply} discharge equipRef:@a-0013 fan freq his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:Hz --- id:@a-0016 dis:Alpha Airside AHU-2 SF VFD Supply Fan Status air cur custom:{supply} discharge equipRef:@a-0013 fan his hisMode:cov kind:Bool point run sensor siteRef:@a-0000 tz:Denver --- id:@a-0017 dis:"Alpha Airside AHU-2 Supply Air Fan S/S Command" air cmd cur custom:{description:"SF VFD S/S" supply} discharge equipRef:@a-0001 fan his hisMode:cov kind:Bool point run siteRef:@a-0000 tz:Denver --- id:@a-0018 dis:Alpha Airside AHU-2 Supply Air Pressure air cur custom:{description:"Duct Static" supply} discharge equipRef:@a-0001 his kind:Number point pressure sensor siteRef:@a-0000 tz:Denver unit:"inH₂O" --- id:@a-0019 dis:Alpha Airside AHU-2 Supply Air Pressure Setpoint air cur custom:{description:"DSP_SP_Curr_Value" supply} discharge equipRef:@a-0001 his kind:Number point pressure siteRef:@a-0000 sp tz:Denver unit:"inH₂O" --- id:@a-001a dis:Alpha Airside AHU-2 Supply Air Temp air cur custom:{description:"SAT" supply} discharge equipRef:@a-0001 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-001b dis:Alpha Airside AHU-2 Supply Air Temp Setpoint air cur custom:{description:"DAT_SP" supply} discharge equipRef:@a-0001 his kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F --- id:@a-001c dis:Alpha Airside AHU-2 Supply Fan Status air cur custom:{description:"SF Status" supply} discharge equipRef:@a-0001 fan his hisMode:cov kind:Bool point run sensor siteRef:@a-0000 tz:Denver --- id:@a-001d dis:Alpha Airside AHU-2 Zone Air Static Pressure air cur custom:{description:"Building DP"} equipRef:@a-0001 his kind:Number point pressure sensor siteRef:@a-0000 tz:Denver unit:"inH₂O" zone --- id:@a-001e dis:Alpha Airside AHU-2 Zone Air Static Pressure Setpoint air cur custom:{description:"Building Static_SP"} equipRef:@a-0001 his kind:Number point pressure siteRef:@a-0000 sp tz:Denver unit:"inH₂O" zone --- id:@a-001f dis:Alpha Airside AHU-2 Zone Occupancy Mode cmd cur custom:{description:"Mode_Occ"} equipRef:@a-0001 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0020 dis:Alpha Airside AHU-3 ahu chilledWaterCooling chilledWaterRef:@a-07b8 elec equip hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 vavZone --- id:@a-0021 dis:Alpha Airside AHU-3 Chilled Water Valve chilled cmd cool cur custom:{description:"Clg_Valve_Cmd"} equipRef:@a-0020 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0022 dis:Alpha Airside AHU-3 Discharge Fan Speed air cmd cur custom:{description:"SF VFD Signal" supply} discharge equipRef:@a-0020 fan his kind:Number point siteRef:@a-0000 speed tz:Denver unit:"%" --- id:@a-0023 dis:Alpha Airside AHU-3 Hot Water Valve cmd cur custom:{description:"Htg_Valve_Cmd"} equipRef:@a-0020 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0024 dis:Alpha Airside AHU-3 Mixed Air Temp air cur custom:{description:"MAT"} equipRef:@a-0020 his kind:Number mixed point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0025 dis:Alpha Airside AHU-3 Outside Air Damper air cmd cur custom:{description:"OSA Damper Signal"} damper equipRef:@a-0020 his kind:Number outside point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0026 dis:Alpha Airside AHU-3 Outside Air Humidity air cur equipRef:@a-0020 his humidity kind:Number outside point sensor siteRef:@a-0000 tz:Denver unit:"%RH" --- id:@a-0027 dis:Alpha Airside AHU-3 Outside Air Temp air cur custom:{dryBulb description:"OAT"} equipRef:@a-0020 his kind:Number outside point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0028 dis:Alpha Airside AHU-3 Relief Air Damper air cmd cur custom:{description:"Relief Damper Signal"} damper equipRef:@a-0020 exhaust his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0029 dis:Alpha Airside AHU-3 Return Air Damper air cmd cur custom:{description:"Rtn Damper Signal"} damper equipRef:@a-0020 his kind:Number point return siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-002a dis:"Alpha Airside AHU-3 Return Air Fan S/S Command" air cmd cur custom:{description:"RF VFD S/S"} equipRef:@a-0020 fan his hisMode:cov kind:Bool point return run siteRef:@a-0000 tz:Denver --- id:@a-002b dis:Alpha Airside AHU-3 Return Air Temp air cur custom:{description:"RAT"} equipRef:@a-0020 his kind:Number point return sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-002c dis:Alpha Airside AHU-3 Return Fan Speed air cmd cur custom:{description:"RF VFD Speed"} equipRef:@a-0020 fan his kind:Number point return siteRef:@a-0000 speed tz:Denver unit:"%" --- id:@a-002d dis:Alpha Airside AHU-3 Return Fan Status air cur custom:{description:"RF Status"} equipRef:@a-0020 fan his hisMode:cov kind:Bool point return run sensor siteRef:@a-0000 tz:Denver --- id:@a-002e dis:"Alpha Airside AHU-3 Supply Air Fan S/S Command" air cmd cur custom:{description:"SF VFD S/S" supply} discharge equipRef:@a-0020 fan his hisMode:cov kind:Bool point run siteRef:@a-0000 tz:Denver --- id:@a-002f dis:Alpha Airside AHU-3 Supply Air Humidity air cur custom:{description:"Supply %RH" supply} discharge equipRef:@a-0020 his humidity kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"%RH" --- id:@a-0030 dis:Alpha Airside AHU-3 Supply Air Humidity Setpoint air cur custom:{description:"Supply %RH SP" supply} discharge equipRef:@a-0020 his humidity kind:Number point siteRef:@a-0000 sp tz:Denver unit:"%RH" --- id:@a-0031 dis:Alpha Airside AHU-3 Supply Air Pressure air cur custom:{description:"Duct Static" supply} discharge equipRef:@a-0020 his kind:Number point pressure sensor siteRef:@a-0000 tz:Denver unit:"inH₂O" --- id:@a-0032 dis:Alpha Airside AHU-3 Supply Air Pressure Setpoint air cur custom:{description:"DSP_SP_Curr_Value" supply} discharge equipRef:@a-0020 his kind:Number point pressure siteRef:@a-0000 sp tz:Denver unit:"inH₂O" --- id:@a-0033 dis:Alpha Airside AHU-3 Supply Air Temp air cur custom:{description:"SAT" supply} discharge equipRef:@a-0020 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0034 dis:Alpha Airside AHU-3 Supply Air Temp Setpoint air cur custom:{description:"DAT_SP" supply} discharge equipRef:@a-0020 his kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F --- id:@a-0035 dis:Alpha Airside AHU-3 Supply Fan Status air cur custom:{description:"SF Status" supply} discharge equipRef:@a-0020 fan his hisMode:cov kind:Bool point run sensor siteRef:@a-0000 tz:Denver --- id:@a-0036 dis:Alpha Airside AHU-3 Zone Air Static Pressure air cur custom:{description:"Building DP"} equipRef:@a-0020 his kind:Number point pressure sensor siteRef:@a-0000 tz:Denver unit:"inH₂O" zone --- id:@a-0037 dis:Alpha Airside AHU-3 Zone Air Static Pressure Setpoint air cur custom:{description:"Building Static_SP"} equipRef:@a-0020 his kind:Number point pressure siteRef:@a-0000 sp tz:Denver unit:"inH₂O" zone --- id:@a-0038 dis:Alpha Airside AHU-3 Zone Occupancy Mode cmd cur custom:{description:"Mode_Occ"} equipRef:@a-0020 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0039 dis:Alpha Airside AHU-4 ahu chilledWaterCooling chilledWaterRef:@a-07b8 dualDuct elec equip hotWaterHeating hotWaterRef:@a-07da hvac siteRef:@a-0000 vavZone --- id:@a-003a dis:Alpha Airside AHU-4 Chilled Water Valve chilled cmd cool cur custom:{description:"Clg_Valve_Cmd"} equipRef:@a-0039 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-003b dis:Alpha Airside AHU-4 Cold Deck Air Temp air coldDeck cur custom:{description:"Cold Deck SAT"} equipRef:@a-0039 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-003c dis:Alpha Airside AHU-4 Cold Deck Air Temp Setpoint air coldDeck cur custom:{description:"Clg SAT SP"} equipRef:@a-0039 his kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F --- id:@a-003d dis:Alpha Airside AHU-4 Discharge Fan Speed air cur custom:{description:"SF_VFD_Curr_Speed" supply} discharge equipRef:@a-0039 fan his kind:Number point sensor siteRef:@a-0000 speed tz:Denver unit:"%" --- id:@a-003e dis:Alpha Airside AHU-4 Hot Deck Air Temp air cur custom:{description:"Hot Deck SAT"} equipRef:@a-0039 his hotDeck kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-003f dis:Alpha Airside AHU-4 Hot Deck Air Temp Setpoint air cur custom:{description:"Htg SAT SP"} equipRef:@a-0039 his hotDeck kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F --- id:@a-0040 dis:Alpha Airside AHU-4 Hot Water Valve cmd cur custom:{description:"Htg_Valve_Cmd"} equipRef:@a-0039 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0041 dis:Alpha Airside AHU-4 Mixed Air Temp air cur custom:{description:"MAT"} equipRef:@a-0039 his kind:Number mixed point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0042 dis:Alpha Airside AHU-4 Outside Air Damper air cmd cur custom:{description:"Econ_Cmd"} damper equipRef:@a-0039 his kind:Number outside point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0043 dis:Alpha Airside AHU-4 Outside Air Temp air cur custom:{dryBulb description:"OAT"} equipRef:@a-0039 his kind:Number outside point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0044 dis:Alpha Airside AHU-4 Relief Air Damper air cmd cur custom:{description:"Relief Signal"} damper equipRef:@a-0039 exhaust his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0045 dis:"Alpha Airside AHU-4 Relief Air Fan S/S Command" air cmd cur custom:{description:"RF VFD S/S" relief} equipRef:@a-0039 exhaust fan his hisMode:cov kind:Bool point run siteRef:@a-0000 tz:Denver --- id:@a-0046 dis:Alpha Airside AHU-4 Relief Fan Status air cur custom:{description:"RF Status" relief} equipRef:@a-0039 exhaust fan his hisMode:cov kind:Bool point run sensor siteRef:@a-0000 tz:Denver --- id:@a-0047 dis:Alpha Airside AHU-4 Return Air Temp air cur custom:{description:"RAT"} equipRef:@a-0039 his kind:Number point return sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0048 dis:"Alpha Airside AHU-4 Supply Air Fan S/S Command" air cmd cur custom:{description:"SF VFD S/S" supply} discharge equipRef:@a-0039 fan his hisMode:cov kind:Bool point run siteRef:@a-0000 tz:Denver --- id:@a-0049 dis:Alpha Airside AHU-4 Supply Air Pressure air cur custom:{description:"Duct Static" supply} discharge equipRef:@a-0039 his kind:Number point pressure sensor siteRef:@a-0000 tz:Denver unit:"inH₂O" --- id:@a-004a dis:Alpha Airside AHU-4 Supply Air Pressure Setpoint air cur custom:{description:"DSP_SP_Curr_Value" supply} discharge equipRef:@a-0039 his kind:Number point pressure siteRef:@a-0000 sp tz:Denver unit:"inH₂O" --- id:@a-004b dis:Alpha Airside AHU-4 Supply Fan Status air cur custom:{description:"SF Status" supply} discharge equipRef:@a-0039 fan his hisMode:cov kind:Bool point run sensor siteRef:@a-0000 tz:Denver --- id:@a-004c dis:Alpha Airside AHU-4 Zone Air Static Pressure air cur custom:{description:"Building Static Reading"} equipRef:@a-0039 his kind:Number point pressure sensor siteRef:@a-0000 tz:Denver unit:"inH₂O" zone --- id:@a-004d dis:Alpha Airside AHU-4 Zone Air Static Pressure air cur custom:{description:"Building Static Sensor"} equipRef:@a-0039 his kind:Number point pressure sensor siteRef:@a-0000 tz:Denver unit:"inH₂O" zone --- id:@a-004e dis:Alpha Airside AHU-4 Zone Air Static Pressure Setpoint air cur custom:{description:"Building Static_SP"} equipRef:@a-0039 his kind:Number point pressure siteRef:@a-0000 sp tz:Denver unit:"inH₂O" zone --- id:@a-004f dis:Alpha Airside AHU-4 Zone Air Temp air cur custom:{description:"IT Room Temp"} equipRef:@a-0039 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0050 dis:Alpha Airside AHU-4 Zone Occupancy Mode cmd cur custom:{description:"Mode_Occ"} equipRef:@a-0039 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0051 dis:Alpha Airside AHU-5 ahu chilledWaterCooling chilledWaterRef:@a-07b8 dualDuct elec equip hotWaterHeating hotWaterRef:@a-07da hvac siteRef:@a-0000 vavZone --- id:@a-0052 dis:Alpha Airside AHU-5 Chilled Water Valve chilled cmd cool cur custom:{description:"Clg_Valve_Cmd"} equipRef:@a-0051 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0053 dis:Alpha Airside AHU-5 Cold Deck Air Temp air coldDeck cur custom:{description:"Cold Deck SAT"} equipRef:@a-0051 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0054 dis:Alpha Airside AHU-5 Cold Deck Air Temp Setpoint air coldDeck cur custom:{description:"Clg SAT SP"} equipRef:@a-0051 his kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F --- id:@a-0055 dis:Alpha Airside AHU-5 Discharge Fan Speed air cur custom:{description:"SF_VFD_Curr_Speed" supply} discharge equipRef:@a-0051 fan his kind:Number point sensor siteRef:@a-0000 speed tz:Denver unit:"%" --- id:@a-0056 dis:Alpha Airside AHU-5 Discharge Fan Speed air cmd cur custom:{description:"SF VFD Signal" supply} discharge equipRef:@a-0051 fan his kind:Number point siteRef:@a-0000 speed tz:Denver unit:"%" --- id:@a-0057 dis:Alpha Airside AHU-5 Hot Deck Air Temp air cur custom:{description:"Hot Deck SAT"} equipRef:@a-0051 his hotDeck kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0058 dis:Alpha Airside AHU-5 Hot Deck Air Temp Setpoint air cur custom:{description:"Htg SAT SP"} equipRef:@a-0051 his hotDeck kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F --- id:@a-0059 dis:Alpha Airside AHU-5 Hot Water Valve cmd cur custom:{description:"Htg_Valve_Cmd"} equipRef:@a-0051 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-005a dis:Alpha Airside AHU-5 Hot Water Valve cmd cur custom:{description:"Htg_Valve_Cmd"} equipRef:@a-0051 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-005b dis:Alpha Airside AHU-5 Mixed Air Temp air cur custom:{description:"MAT"} equipRef:@a-0051 his kind:Number mixed point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-005c dis:Alpha Airside AHU-5 Outside Air Damper Cmd air cmd cur custom:{description:"Econ_Cmd"} damper equipRef:@a-0051 his kind:Number outside point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-005d dis:Alpha Airside AHU-5 Outside Air Damper Signal air cmd cur custom:{description:"OSA Damper Signal"} damper equipRef:@a-0051 his kind:Number outside point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-005e dis:Alpha Airside AHU-5 Outside Air Temp air cur custom:{dryBulb description:"OAT"} equipRef:@a-0051 his kind:Number outside point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-005f dis:Alpha Airside AHU-5 Relief Air Damper air cmd cur custom:{description:"Relief Signal"} damper equipRef:@a-0051 exhaust his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0060 dis:Alpha Airside AHU-5 Return Air Damper Signal air cmd cur custom:{description:"Rtn Damper Signal"} damper equipRef:@a-0051 his kind:Number point return siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0061 dis:"Alpha Airside AHU-5 Return Air Fan S/S Command" air cmd cur custom:{description:"RF VFD S/S"} equipRef:@a-0051 fan his hisMode:cov kind:Bool point return run siteRef:@a-0000 tz:Denver --- id:@a-0062 dis:Alpha Airside AHU-5 Return Air Temp air cur custom:{description:"RAT"} equipRef:@a-0051 his kind:Number point return sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0063 dis:Alpha Airside AHU-5 Return Fan Status air cur custom:{description:"RF Status"} equipRef:@a-0051 fan his hisMode:cov kind:Bool point return run sensor siteRef:@a-0000 tz:Denver --- id:@a-0064 dis:"Alpha Airside AHU-5 Supply Air Fan S/S Command" air cmd cur custom:{description:"SF VFD S/S" supply} discharge equipRef:@a-0051 fan his hisMode:cov kind:Bool point run siteRef:@a-0000 tz:Denver --- id:@a-0065 dis:Alpha Airside AHU-5 Supply Air Pressure air cur custom:{description:"Duct Static" supply} discharge equipRef:@a-0051 his kind:Number point pressure sensor siteRef:@a-0000 tz:Denver unit:"inH₂O" --- id:@a-0066 dis:Alpha Airside AHU-5 Supply Air Pressure Setpoint air cur custom:{description:"DSP_SP_Curr_Value" supply} discharge equipRef:@a-0051 his kind:Number point pressure siteRef:@a-0000 sp tz:Denver unit:"inH₂O" --- id:@a-0067 dis:Alpha Airside AHU-5 Supply Fan Status air cur custom:{description:"SF Status" supply} discharge equipRef:@a-0051 fan his hisMode:cov kind:Bool point run sensor siteRef:@a-0000 tz:Denver --- id:@a-0068 dis:Alpha Airside AHU-5 Zone Air Static Pressure air cur custom:{description:"Building DP"} equipRef:@a-0051 his kind:Number point pressure sensor siteRef:@a-0000 tz:Denver unit:"inH₂O" zone --- id:@a-0069 dis:Alpha Airside AHU-5 Zone Air Static Pressure Setpoint air cur custom:{description:"Building Static_SP"} equipRef:@a-0051 his kind:Number point pressure siteRef:@a-0000 sp tz:Denver unit:"inH₂O" zone --- id:@a-006a dis:Alpha Airside AHU-5 Zone Occupancy Mode cmd cur custom:{description:"Mode_Occ"} equipRef:@a-0051 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-006b dis:Alpha Airside DD 1-4-1 airRef:@a-0039 dualDuct equip equipRef:@a-0039 fanPowered hvac siteRef:@a-0000 thermostat vav --- id:@a-006c dis:Alpha Airside DD 1-4-1 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-006b his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-006d dis:Alpha Airside DD 1-4-1 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-006b flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-006e dis:Alpha Airside DD 1-4-1 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-006b flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-006f dis:Alpha Airside DD 1-4-1 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-006b his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0070 dis:Alpha Airside DD 1-4-1 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-006b his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0071 dis:Alpha Airside DD 1-4-1 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-006b flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0072 dis:Alpha Airside DD 1-4-1 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-006b flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0073 dis:Alpha Airside DD 1-4-1 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-006b his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0074 dis:Alpha Airside DD 1-4-1 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-006b his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0075 dis:Alpha Airside DD 1-4-1 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-006b heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0076 dis:Alpha Airside DD 1-4-1 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-006b his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0077 dis:Alpha Airside DD 1-4-1 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-006b heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0078 dis:Alpha Airside DD 1-4-1 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-006b his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0079 dis:Alpha Airside DD 1-4-10 airRef:@a-0039 dualDuct equip equipRef:@a-0039 hvac siteRef:@a-0000 thermostat vav --- id:@a-007a dis:Alpha Airside DD 1-4-10 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-0079 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-007b dis:Alpha Airside DD 1-4-10 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-0079 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-007c dis:Alpha Airside DD 1-4-10 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-0079 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-007d dis:Alpha Airside DD 1-4-10 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0079 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-007e dis:Alpha Airside DD 1-4-10 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-0079 his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-007f dis:Alpha Airside DD 1-4-10 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-0079 flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0080 dis:Alpha Airside DD 1-4-10 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-0079 flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0081 dis:Alpha Airside DD 1-4-10 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0079 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0082 dis:Alpha Airside DD 1-4-10 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0079 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0083 dis:Alpha Airside DD 1-4-10 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0079 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0084 dis:Alpha Airside DD 1-4-10 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0079 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0085 dis:Alpha Airside DD 1-4-10 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0079 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0086 dis:Alpha Airside DD 1-4-10 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0079 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0087 dis:Alpha Airside DD 1-4-11 airRef:@a-0039 dualDuct equip equipRef:@a-0039 hvac siteRef:@a-0000 thermostat vav --- id:@a-0088 dis:Alpha Airside DD 1-4-11 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-0087 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0089 dis:Alpha Airside DD 1-4-11 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-0087 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-008a dis:Alpha Airside DD 1-4-11 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-0087 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-008b dis:Alpha Airside DD 1-4-11 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0087 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-008c dis:Alpha Airside DD 1-4-11 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-0087 his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-008d dis:Alpha Airside DD 1-4-11 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-0087 flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-008e dis:Alpha Airside DD 1-4-11 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-0087 flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-008f dis:Alpha Airside DD 1-4-11 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0087 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0090 dis:Alpha Airside DD 1-4-11 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0087 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0091 dis:Alpha Airside DD 1-4-11 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0087 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0092 dis:Alpha Airside DD 1-4-11 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0087 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0093 dis:Alpha Airside DD 1-4-11 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0087 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0094 dis:Alpha Airside DD 1-4-11 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0087 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0095 dis:Alpha Airside DD 1-4-12 airRef:@a-0039 dualDuct equip equipRef:@a-0039 fanPowered hvac siteRef:@a-0000 thermostat vav --- id:@a-0096 dis:Alpha Airside DD 1-4-12 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-0095 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0097 dis:Alpha Airside DD 1-4-12 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-0095 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0098 dis:Alpha Airside DD 1-4-12 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-0095 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0099 dis:Alpha Airside DD 1-4-12 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0095 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-009a dis:Alpha Airside DD 1-4-12 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-0095 his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-009b dis:Alpha Airside DD 1-4-12 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-0095 flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-009c dis:Alpha Airside DD 1-4-12 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-0095 flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-009d dis:Alpha Airside DD 1-4-12 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0095 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-009e dis:Alpha Airside DD 1-4-12 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0095 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-009f dis:Alpha Airside DD 1-4-12 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0095 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-00a0 dis:Alpha Airside DD 1-4-12 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0095 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-00a1 dis:Alpha Airside DD 1-4-12 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0095 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-00a2 dis:Alpha Airside DD 1-4-12 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0095 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-00a3 dis:Alpha Airside DD 1-4-13 airRef:@a-0039 dualDuct equip equipRef:@a-0039 fanPowered hvac siteRef:@a-0000 thermostat vav --- id:@a-00a4 dis:Alpha Airside DD 1-4-13 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-00a3 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-00a5 dis:Alpha Airside DD 1-4-13 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-00a3 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-00a6 dis:Alpha Airside DD 1-4-13 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-00a3 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-00a7 dis:Alpha Airside DD 1-4-13 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-00a3 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-00a8 dis:Alpha Airside DD 1-4-13 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-00a3 his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-00a9 dis:Alpha Airside DD 1-4-13 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-00a3 flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-00aa dis:Alpha Airside DD 1-4-13 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-00a3 flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-00ab dis:Alpha Airside DD 1-4-13 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-00a3 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-00ac dis:Alpha Airside DD 1-4-13 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-00a3 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-00ad dis:Alpha Airside DD 1-4-13 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-00a3 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-00ae dis:Alpha Airside DD 1-4-13 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-00a3 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-00af dis:Alpha Airside DD 1-4-13 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-00a3 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-00b0 dis:Alpha Airside DD 1-4-13 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-00a3 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-00b1 dis:Alpha Airside DD 1-4-14 airRef:@a-0039 dualDuct equip equipRef:@a-0039 fanPowered hvac siteRef:@a-0000 thermostat vav --- id:@a-00b2 dis:Alpha Airside DD 1-4-14 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-00b1 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-00b3 dis:Alpha Airside DD 1-4-14 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-00b1 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-00b4 dis:Alpha Airside DD 1-4-14 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-00b1 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-00b5 dis:Alpha Airside DD 1-4-14 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-00b1 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-00b6 dis:Alpha Airside DD 1-4-14 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-00b1 his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-00b7 dis:Alpha Airside DD 1-4-14 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-00b1 flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-00b8 dis:Alpha Airside DD 1-4-14 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-00b1 flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-00b9 dis:Alpha Airside DD 1-4-14 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-00b1 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-00ba dis:Alpha Airside DD 1-4-14 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-00b1 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-00bb dis:Alpha Airside DD 1-4-14 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-00b1 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-00bc dis:Alpha Airside DD 1-4-14 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-00b1 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-00bd dis:Alpha Airside DD 1-4-14 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-00b1 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-00be dis:Alpha Airside DD 1-4-14 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-00b1 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-00bf dis:Alpha Airside DD 1-4-2 airRef:@a-0039 dualDuct equip equipRef:@a-0039 hvac siteRef:@a-0000 thermostat vav --- id:@a-00c0 dis:Alpha Airside DD 1-4-2 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-00bf his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-00c1 dis:Alpha Airside DD 1-4-2 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-00bf flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-00c2 dis:Alpha Airside DD 1-4-2 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-00bf flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-00c3 dis:Alpha Airside DD 1-4-2 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-00bf his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-00c4 dis:Alpha Airside DD 1-4-2 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-00bf his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-00c5 dis:Alpha Airside DD 1-4-2 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-00bf flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-00c6 dis:Alpha Airside DD 1-4-2 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-00bf flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-00c7 dis:Alpha Airside DD 1-4-2 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-00bf his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-00c8 dis:Alpha Airside DD 1-4-2 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-00bf his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-00c9 dis:Alpha Airside DD 1-4-2 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-00bf heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-00ca dis:Alpha Airside DD 1-4-2 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-00bf his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-00cb dis:Alpha Airside DD 1-4-2 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-00bf heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-00cc dis:Alpha Airside DD 1-4-2 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-00bf his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-00cd dis:Alpha Airside DD 1-4-3 airRef:@a-0039 dualDuct equip equipRef:@a-0039 hvac siteRef:@a-0000 thermostat vav --- id:@a-00ce dis:Alpha Airside DD 1-4-3 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-00cd his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-00cf dis:Alpha Airside DD 1-4-3 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-00cd flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-00d0 dis:Alpha Airside DD 1-4-3 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-00cd flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-00d1 dis:Alpha Airside DD 1-4-3 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-00cd his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-00d2 dis:Alpha Airside DD 1-4-3 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-00cd his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-00d3 dis:Alpha Airside DD 1-4-3 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-00cd flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-00d4 dis:Alpha Airside DD 1-4-3 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-00cd flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-00d5 dis:Alpha Airside DD 1-4-3 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-00cd his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-00d6 dis:Alpha Airside DD 1-4-3 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-00cd his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-00d7 dis:Alpha Airside DD 1-4-3 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-00cd heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-00d8 dis:Alpha Airside DD 1-4-3 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-00cd his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-00d9 dis:Alpha Airside DD 1-4-3 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-00cd heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-00da dis:Alpha Airside DD 1-4-3 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-00cd his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-00db dis:Alpha Airside DD 1-4-4 airRef:@a-0039 dualDuct equip equipRef:@a-0039 hvac siteRef:@a-0000 thermostat vav --- id:@a-00dc dis:Alpha Airside DD 1-4-4 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-00db his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-00dd dis:Alpha Airside DD 1-4-4 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-00db flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-00de dis:Alpha Airside DD 1-4-4 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-00db flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-00df dis:Alpha Airside DD 1-4-4 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-00db his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-00e0 dis:Alpha Airside DD 1-4-4 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-00db his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-00e1 dis:Alpha Airside DD 1-4-4 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-00db flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-00e2 dis:Alpha Airside DD 1-4-4 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-00db flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-00e3 dis:Alpha Airside DD 1-4-4 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-00db his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-00e4 dis:Alpha Airside DD 1-4-4 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-00db his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-00e5 dis:Alpha Airside DD 1-4-4 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-00db heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-00e6 dis:Alpha Airside DD 1-4-4 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-00db his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-00e7 dis:Alpha Airside DD 1-4-4 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-00db heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-00e8 dis:Alpha Airside DD 1-4-4 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-00db his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-00e9 dis:Alpha Airside DD 1-4-5 airRef:@a-0039 dualDuct equip equipRef:@a-0039 fanPowered hvac siteRef:@a-0000 thermostat vav --- id:@a-00ea dis:Alpha Airside DD 1-4-5 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-00e9 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-00eb dis:Alpha Airside DD 1-4-5 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-00e9 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-00ec dis:Alpha Airside DD 1-4-5 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-00e9 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-00ed dis:Alpha Airside DD 1-4-5 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-00e9 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-00ee dis:Alpha Airside DD 1-4-5 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-00e9 his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-00ef dis:Alpha Airside DD 1-4-5 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-00e9 flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-00f0 dis:Alpha Airside DD 1-4-5 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-00e9 flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-00f1 dis:Alpha Airside DD 1-4-5 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-00e9 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-00f2 dis:Alpha Airside DD 1-4-5 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-00e9 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-00f3 dis:Alpha Airside DD 1-4-5 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-00e9 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-00f4 dis:Alpha Airside DD 1-4-5 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-00e9 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-00f5 dis:Alpha Airside DD 1-4-5 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-00e9 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-00f6 dis:Alpha Airside DD 1-4-5 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-00e9 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-00f7 dis:Alpha Airside DD 1-4-6 airRef:@a-0039 dualDuct equip equipRef:@a-0039 hvac siteRef:@a-0000 thermostat vav --- id:@a-00f8 dis:Alpha Airside DD 1-4-6 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-00f7 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-00f9 dis:Alpha Airside DD 1-4-6 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-00f7 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-00fa dis:Alpha Airside DD 1-4-6 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-00f7 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-00fb dis:Alpha Airside DD 1-4-6 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-00f7 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-00fc dis:Alpha Airside DD 1-4-6 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-00f7 his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-00fd dis:Alpha Airside DD 1-4-6 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-00f7 flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-00fe dis:Alpha Airside DD 1-4-6 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-00f7 flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-00ff dis:Alpha Airside DD 1-4-6 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-00f7 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0100 dis:Alpha Airside DD 1-4-6 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-00f7 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0101 dis:Alpha Airside DD 1-4-6 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-00f7 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0102 dis:Alpha Airside DD 1-4-6 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-00f7 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0103 dis:Alpha Airside DD 1-4-6 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-00f7 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0104 dis:Alpha Airside DD 1-4-6 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-00f7 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0105 dis:Alpha Airside DD 1-4-7 airRef:@a-0039 dualDuct equip equipRef:@a-0039 hvac siteRef:@a-0000 thermostat vav --- id:@a-0106 dis:Alpha Airside DD 1-4-7 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-0105 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0107 dis:Alpha Airside DD 1-4-7 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-0105 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0108 dis:Alpha Airside DD 1-4-7 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-0105 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0109 dis:Alpha Airside DD 1-4-7 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0105 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-010a dis:Alpha Airside DD 1-4-7 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-0105 his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-010b dis:Alpha Airside DD 1-4-7 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-0105 flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-010c dis:Alpha Airside DD 1-4-7 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-0105 flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-010d dis:Alpha Airside DD 1-4-7 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0105 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-010e dis:Alpha Airside DD 1-4-7 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0105 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-010f dis:Alpha Airside DD 1-4-7 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0105 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0110 dis:Alpha Airside DD 1-4-7 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0105 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0111 dis:Alpha Airside DD 1-4-7 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0105 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0112 dis:Alpha Airside DD 1-4-7 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0105 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0113 dis:Alpha Airside DD 1-4-8 airRef:@a-0039 dualDuct equip equipRef:@a-0039 hvac siteRef:@a-0000 thermostat vav --- id:@a-0114 dis:Alpha Airside DD 1-4-8 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-0113 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0115 dis:Alpha Airside DD 1-4-8 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-0113 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0116 dis:Alpha Airside DD 1-4-8 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-0113 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0117 dis:Alpha Airside DD 1-4-8 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0113 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0118 dis:Alpha Airside DD 1-4-8 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-0113 his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0119 dis:Alpha Airside DD 1-4-8 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-0113 flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-011a dis:Alpha Airside DD 1-4-8 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-0113 flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-011b dis:Alpha Airside DD 1-4-8 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0113 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-011c dis:Alpha Airside DD 1-4-8 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0113 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-011d dis:Alpha Airside DD 1-4-8 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0113 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-011e dis:Alpha Airside DD 1-4-8 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0113 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-011f dis:Alpha Airside DD 1-4-8 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0113 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0120 dis:Alpha Airside DD 1-4-8 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0113 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0121 dis:Alpha Airside DD 1-4-9 airRef:@a-0039 dualDuct equip equipRef:@a-0039 fanPowered hvac siteRef:@a-0000 thermostat vav --- id:@a-0122 dis:Alpha Airside DD 1-4-9 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-0121 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0123 dis:Alpha Airside DD 1-4-9 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-0121 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0124 dis:Alpha Airside DD 1-4-9 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-0121 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0125 dis:Alpha Airside DD 1-4-9 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0121 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0126 dis:Alpha Airside DD 1-4-9 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-0121 his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0127 dis:Alpha Airside DD 1-4-9 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-0121 flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0128 dis:Alpha Airside DD 1-4-9 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-0121 flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0129 dis:Alpha Airside DD 1-4-9 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0121 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-012a dis:Alpha Airside DD 1-4-9 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0121 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-012b dis:Alpha Airside DD 1-4-9 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0121 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-012c dis:Alpha Airside DD 1-4-9 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0121 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-012d dis:Alpha Airside DD 1-4-9 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0121 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-012e dis:Alpha Airside DD 1-4-9 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0121 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-012f dis:Alpha Airside DD 1-5-1 airRef:@a-0051 dualDuct equip equipRef:@a-0051 fanPowered hvac siteRef:@a-0000 thermostat vav --- id:@a-0130 dis:Alpha Airside DD 1-5-1 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-012f his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0131 dis:Alpha Airside DD 1-5-1 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-012f flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0132 dis:Alpha Airside DD 1-5-1 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-012f flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0133 dis:Alpha Airside DD 1-5-1 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-012f his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0134 dis:Alpha Airside DD 1-5-1 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-012f his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0135 dis:Alpha Airside DD 1-5-1 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-012f flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0136 dis:Alpha Airside DD 1-5-1 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-012f flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0137 dis:Alpha Airside DD 1-5-1 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-012f his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0138 dis:Alpha Airside DD 1-5-1 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-012f his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0139 dis:Alpha Airside DD 1-5-1 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-012f heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-013a dis:Alpha Airside DD 1-5-1 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-012f his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-013b dis:Alpha Airside DD 1-5-1 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-012f heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-013c dis:Alpha Airside DD 1-5-1 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-012f his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-013d dis:Alpha Airside DD 1-5-10 airRef:@a-0051 dualDuct equip equipRef:@a-0051 fanPowered hvac siteRef:@a-0000 thermostat vav --- id:@a-013e dis:Alpha Airside DD 1-5-10 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-013d his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-013f dis:Alpha Airside DD 1-5-10 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-013d flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0140 dis:Alpha Airside DD 1-5-10 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-013d flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0141 dis:Alpha Airside DD 1-5-10 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-013d his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0142 dis:Alpha Airside DD 1-5-10 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-013d his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0143 dis:Alpha Airside DD 1-5-10 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-013d flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0144 dis:Alpha Airside DD 1-5-10 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-013d flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0145 dis:Alpha Airside DD 1-5-10 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-013d his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0146 dis:Alpha Airside DD 1-5-10 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-013d his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0147 dis:Alpha Airside DD 1-5-10 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-013d heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0148 dis:Alpha Airside DD 1-5-10 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-013d his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0149 dis:Alpha Airside DD 1-5-10 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-013d heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-014a dis:Alpha Airside DD 1-5-10 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-013d his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-014b dis:Alpha Airside DD 1-5-11 airRef:@a-0051 dualDuct equip equipRef:@a-0051 fanPowered hvac siteRef:@a-0000 thermostat vav --- id:@a-014c dis:Alpha Airside DD 1-5-11 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-014b his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-014d dis:Alpha Airside DD 1-5-11 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-014b flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-014e dis:Alpha Airside DD 1-5-11 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-014b flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-014f dis:Alpha Airside DD 1-5-11 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-014b his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0150 dis:Alpha Airside DD 1-5-11 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-014b his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0151 dis:Alpha Airside DD 1-5-11 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-014b flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0152 dis:Alpha Airside DD 1-5-11 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-014b flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0153 dis:Alpha Airside DD 1-5-11 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-014b his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0154 dis:Alpha Airside DD 1-5-11 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-014b his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0155 dis:Alpha Airside DD 1-5-11 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-014b heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0156 dis:Alpha Airside DD 1-5-11 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-014b his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0157 dis:Alpha Airside DD 1-5-11 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-014b heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0158 dis:Alpha Airside DD 1-5-11 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-014b his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0159 dis:Alpha Airside DD 1-5-12 airRef:@a-0051 dualDuct equip equipRef:@a-0051 fanPowered hvac siteRef:@a-0000 thermostat vav --- id:@a-015a dis:Alpha Airside DD 1-5-12 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-0159 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-015b dis:Alpha Airside DD 1-5-12 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-0159 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-015c dis:Alpha Airside DD 1-5-12 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-0159 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-015d dis:Alpha Airside DD 1-5-12 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0159 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-015e dis:Alpha Airside DD 1-5-12 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-0159 his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-015f dis:Alpha Airside DD 1-5-12 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-0159 flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0160 dis:Alpha Airside DD 1-5-12 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-0159 flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0161 dis:Alpha Airside DD 1-5-12 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0159 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0162 dis:Alpha Airside DD 1-5-12 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0159 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0163 dis:Alpha Airside DD 1-5-12 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0159 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0164 dis:Alpha Airside DD 1-5-12 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0159 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0165 dis:Alpha Airside DD 1-5-12 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0159 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0166 dis:Alpha Airside DD 1-5-12 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0159 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0167 dis:Alpha Airside DD 1-5-13 airRef:@a-0051 dualDuct equip equipRef:@a-0051 fanPowered hvac siteRef:@a-0000 thermostat vav --- id:@a-0168 dis:Alpha Airside DD 1-5-13 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-0167 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0169 dis:Alpha Airside DD 1-5-13 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-0167 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-016a dis:Alpha Airside DD 1-5-13 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-0167 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-016b dis:Alpha Airside DD 1-5-13 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0167 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-016c dis:Alpha Airside DD 1-5-13 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-0167 his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-016d dis:Alpha Airside DD 1-5-13 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-0167 flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-016e dis:Alpha Airside DD 1-5-13 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-0167 flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-016f dis:Alpha Airside DD 1-5-13 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0167 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0170 dis:Alpha Airside DD 1-5-13 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0167 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0171 dis:Alpha Airside DD 1-5-13 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0167 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0172 dis:Alpha Airside DD 1-5-13 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0167 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0173 dis:Alpha Airside DD 1-5-13 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0167 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0174 dis:Alpha Airside DD 1-5-13 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0167 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0175 dis:Alpha Airside DD 1-5-14 airRef:@a-0051 dualDuct equip equipRef:@a-0051 hvac siteRef:@a-0000 thermostat vav --- id:@a-0176 dis:Alpha Airside DD 1-5-14 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-0175 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0177 dis:Alpha Airside DD 1-5-14 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-0175 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0178 dis:Alpha Airside DD 1-5-14 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-0175 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0179 dis:Alpha Airside DD 1-5-14 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0175 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-017a dis:Alpha Airside DD 1-5-14 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-0175 his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-017b dis:Alpha Airside DD 1-5-14 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-0175 flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-017c dis:Alpha Airside DD 1-5-14 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-0175 flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-017d dis:Alpha Airside DD 1-5-14 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0175 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-017e dis:Alpha Airside DD 1-5-14 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0175 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-017f dis:Alpha Airside DD 1-5-14 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0175 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0180 dis:Alpha Airside DD 1-5-14 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0175 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0181 dis:Alpha Airside DD 1-5-14 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0175 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0182 dis:Alpha Airside DD 1-5-14 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0175 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0183 dis:Alpha Airside DD 1-5-15 airRef:@a-0051 dualDuct equip equipRef:@a-0051 fanPowered hvac siteRef:@a-0000 thermostat vav --- id:@a-0184 dis:Alpha Airside DD 1-5-15 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-0183 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0185 dis:Alpha Airside DD 1-5-15 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-0183 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0186 dis:Alpha Airside DD 1-5-15 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-0183 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0187 dis:Alpha Airside DD 1-5-15 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0183 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0188 dis:Alpha Airside DD 1-5-15 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-0183 his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0189 dis:Alpha Airside DD 1-5-15 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-0183 flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-018a dis:Alpha Airside DD 1-5-15 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-0183 flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-018b dis:Alpha Airside DD 1-5-15 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0183 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-018c dis:Alpha Airside DD 1-5-15 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0183 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-018d dis:Alpha Airside DD 1-5-15 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0183 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-018e dis:Alpha Airside DD 1-5-15 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0183 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-018f dis:Alpha Airside DD 1-5-15 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0183 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0190 dis:Alpha Airside DD 1-5-15 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0183 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0191 dis:Alpha Airside DD 1-5-16 airRef:@a-0051 dualDuct equip equipRef:@a-0051 hvac siteRef:@a-0000 thermostat vav --- id:@a-0192 dis:Alpha Airside DD 1-5-16 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-0191 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0193 dis:Alpha Airside DD 1-5-16 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-0191 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0194 dis:Alpha Airside DD 1-5-16 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-0191 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0195 dis:Alpha Airside DD 1-5-16 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0191 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0196 dis:Alpha Airside DD 1-5-16 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-0191 his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0197 dis:Alpha Airside DD 1-5-16 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-0191 flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0198 dis:Alpha Airside DD 1-5-16 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-0191 flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0199 dis:Alpha Airside DD 1-5-16 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0191 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-019a dis:Alpha Airside DD 1-5-16 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0191 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-019b dis:Alpha Airside DD 1-5-16 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0191 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-019c dis:Alpha Airside DD 1-5-16 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0191 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-019d dis:Alpha Airside DD 1-5-16 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0191 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-019e dis:Alpha Airside DD 1-5-16 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0191 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-019f dis:Alpha Airside DD 1-5-17 airRef:@a-0051 dualDuct equip equipRef:@a-0051 fanPowered hvac siteRef:@a-0000 thermostat vav --- id:@a-01a0 dis:Alpha Airside DD 1-5-17 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-019f his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-01a1 dis:Alpha Airside DD 1-5-17 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-019f flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-01a2 dis:Alpha Airside DD 1-5-17 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-019f flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-01a3 dis:Alpha Airside DD 1-5-17 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-019f his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-01a4 dis:Alpha Airside DD 1-5-17 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-019f his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-01a5 dis:Alpha Airside DD 1-5-17 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-019f flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-01a6 dis:Alpha Airside DD 1-5-17 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-019f flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-01a7 dis:Alpha Airside DD 1-5-17 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-019f his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-01a8 dis:Alpha Airside DD 1-5-17 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-019f his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-01a9 dis:Alpha Airside DD 1-5-17 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-019f heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-01aa dis:Alpha Airside DD 1-5-17 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-019f his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-01ab dis:Alpha Airside DD 1-5-17 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-019f heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-01ac dis:Alpha Airside DD 1-5-17 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-019f his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-01ad dis:Alpha Airside DD 1-5-18 airRef:@a-0051 dualDuct equip equipRef:@a-0051 hvac siteRef:@a-0000 thermostat vav --- id:@a-01ae dis:Alpha Airside DD 1-5-18 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-01ad his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-01af dis:Alpha Airside DD 1-5-18 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-01ad flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-01b0 dis:Alpha Airside DD 1-5-18 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-01ad flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-01b1 dis:Alpha Airside DD 1-5-18 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-01ad his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-01b2 dis:Alpha Airside DD 1-5-18 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-01ad his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-01b3 dis:Alpha Airside DD 1-5-18 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-01ad flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-01b4 dis:Alpha Airside DD 1-5-18 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-01ad flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-01b5 dis:Alpha Airside DD 1-5-18 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-01ad his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-01b6 dis:Alpha Airside DD 1-5-18 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-01ad his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-01b7 dis:Alpha Airside DD 1-5-18 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-01ad heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-01b8 dis:Alpha Airside DD 1-5-18 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-01ad his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-01b9 dis:Alpha Airside DD 1-5-18 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-01ad heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-01ba dis:Alpha Airside DD 1-5-18 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-01ad his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-01bb dis:Alpha Airside DD 1-5-19 airRef:@a-0051 dualDuct equip equipRef:@a-0051 hvac siteRef:@a-0000 thermostat vav --- id:@a-01bc dis:Alpha Airside DD 1-5-19 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-01bb his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-01bd dis:Alpha Airside DD 1-5-19 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-01bb flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-01be dis:Alpha Airside DD 1-5-19 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-01bb flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-01bf dis:Alpha Airside DD 1-5-19 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-01bb his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-01c0 dis:Alpha Airside DD 1-5-19 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-01bb his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-01c1 dis:Alpha Airside DD 1-5-19 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-01bb flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-01c2 dis:Alpha Airside DD 1-5-19 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-01bb flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-01c3 dis:Alpha Airside DD 1-5-19 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-01bb his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-01c4 dis:Alpha Airside DD 1-5-19 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-01bb his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-01c5 dis:Alpha Airside DD 1-5-19 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-01bb heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-01c6 dis:Alpha Airside DD 1-5-19 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-01bb his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-01c7 dis:Alpha Airside DD 1-5-19 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-01bb heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-01c8 dis:Alpha Airside DD 1-5-19 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-01bb his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-01c9 dis:Alpha Airside DD 1-5-2 airRef:@a-0051 dualDuct equip equipRef:@a-0051 fanPowered hvac siteRef:@a-0000 thermostat vav --- id:@a-01ca dis:Alpha Airside DD 1-5-2 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-01c9 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-01cb dis:Alpha Airside DD 1-5-2 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-01c9 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-01cc dis:Alpha Airside DD 1-5-2 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-01c9 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-01cd dis:Alpha Airside DD 1-5-2 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-01c9 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-01ce dis:Alpha Airside DD 1-5-2 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-01c9 his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-01cf dis:Alpha Airside DD 1-5-2 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-01c9 flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-01d0 dis:Alpha Airside DD 1-5-2 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-01c9 flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-01d1 dis:Alpha Airside DD 1-5-2 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-01c9 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-01d2 dis:Alpha Airside DD 1-5-2 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-01c9 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-01d3 dis:Alpha Airside DD 1-5-2 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-01c9 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-01d4 dis:Alpha Airside DD 1-5-2 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-01c9 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-01d5 dis:Alpha Airside DD 1-5-2 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-01c9 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-01d6 dis:Alpha Airside DD 1-5-2 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-01c9 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-01d7 dis:Alpha Airside DD 1-5-3 airRef:@a-0051 dualDuct equip equipRef:@a-0051 hvac siteRef:@a-0000 thermostat vav --- id:@a-01d8 dis:Alpha Airside DD 1-5-3 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-01d7 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-01d9 dis:Alpha Airside DD 1-5-3 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-01d7 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-01da dis:Alpha Airside DD 1-5-3 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-01d7 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-01db dis:Alpha Airside DD 1-5-3 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-01d7 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-01dc dis:Alpha Airside DD 1-5-3 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-01d7 his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-01dd dis:Alpha Airside DD 1-5-3 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-01d7 flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-01de dis:Alpha Airside DD 1-5-3 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-01d7 flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-01df dis:Alpha Airside DD 1-5-3 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-01d7 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-01e0 dis:Alpha Airside DD 1-5-3 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-01d7 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-01e1 dis:Alpha Airside DD 1-5-3 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-01d7 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-01e2 dis:Alpha Airside DD 1-5-3 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-01d7 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-01e3 dis:Alpha Airside DD 1-5-3 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-01d7 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-01e4 dis:Alpha Airside DD 1-5-3 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-01d7 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-01e5 dis:Alpha Airside DD 1-5-4 airRef:@a-0051 dualDuct equip equipRef:@a-0051 fanPowered hvac siteRef:@a-0000 thermostat vav --- id:@a-01e6 dis:Alpha Airside DD 1-5-4 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-01e5 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-01e7 dis:Alpha Airside DD 1-5-4 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-01e5 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-01e8 dis:Alpha Airside DD 1-5-4 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-01e5 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-01e9 dis:Alpha Airside DD 1-5-4 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-01e5 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-01ea dis:Alpha Airside DD 1-5-4 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-01e5 his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-01eb dis:Alpha Airside DD 1-5-4 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-01e5 flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-01ec dis:Alpha Airside DD 1-5-4 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-01e5 flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-01ed dis:Alpha Airside DD 1-5-4 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-01e5 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-01ee dis:Alpha Airside DD 1-5-4 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-01e5 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-01ef dis:Alpha Airside DD 1-5-4 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-01e5 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-01f0 dis:Alpha Airside DD 1-5-4 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-01e5 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-01f1 dis:Alpha Airside DD 1-5-4 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-01e5 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-01f2 dis:Alpha Airside DD 1-5-4 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-01e5 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-01f3 dis:Alpha Airside DD 1-5-5 airRef:@a-0051 dualDuct equip equipRef:@a-0051 fanPowered hvac siteRef:@a-0000 thermostat vav --- id:@a-01f4 dis:Alpha Airside DD 1-5-5 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-01f3 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-01f5 dis:Alpha Airside DD 1-5-5 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-01f3 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-01f6 dis:Alpha Airside DD 1-5-5 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-01f3 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-01f7 dis:Alpha Airside DD 1-5-5 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-01f3 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-01f8 dis:Alpha Airside DD 1-5-5 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-01f3 his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-01f9 dis:Alpha Airside DD 1-5-5 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-01f3 flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-01fa dis:Alpha Airside DD 1-5-5 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-01f3 flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-01fb dis:Alpha Airside DD 1-5-5 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-01f3 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-01fc dis:Alpha Airside DD 1-5-5 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-01f3 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-01fd dis:Alpha Airside DD 1-5-5 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-01f3 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-01fe dis:Alpha Airside DD 1-5-5 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-01f3 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-01ff dis:Alpha Airside DD 1-5-5 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-01f3 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0200 dis:Alpha Airside DD 1-5-5 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-01f3 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0201 dis:Alpha Airside DD 1-5-6 airRef:@a-0051 dualDuct equip equipRef:@a-0051 fanPowered hvac siteRef:@a-0000 thermostat vav --- id:@a-0202 dis:Alpha Airside DD 1-5-6 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-0201 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0203 dis:Alpha Airside DD 1-5-6 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-0201 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0204 dis:Alpha Airside DD 1-5-6 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-0201 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0205 dis:Alpha Airside DD 1-5-6 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0201 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0206 dis:Alpha Airside DD 1-5-6 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-0201 his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0207 dis:Alpha Airside DD 1-5-6 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-0201 flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0208 dis:Alpha Airside DD 1-5-6 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-0201 flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0209 dis:Alpha Airside DD 1-5-6 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0201 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-020a dis:Alpha Airside DD 1-5-6 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0201 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-020b dis:Alpha Airside DD 1-5-6 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0201 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-020c dis:Alpha Airside DD 1-5-6 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0201 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-020d dis:Alpha Airside DD 1-5-6 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0201 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-020e dis:Alpha Airside DD 1-5-6 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0201 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-020f dis:Alpha Airside DD 1-5-7 airRef:@a-0051 dualDuct equip equipRef:@a-0051 hvac siteRef:@a-0000 thermostat vav --- id:@a-0210 dis:Alpha Airside DD 1-5-7 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-020f his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0211 dis:Alpha Airside DD 1-5-7 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-020f flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0212 dis:Alpha Airside DD 1-5-7 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-020f flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0213 dis:Alpha Airside DD 1-5-7 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-020f his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0214 dis:Alpha Airside DD 1-5-7 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-020f his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0215 dis:Alpha Airside DD 1-5-7 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-020f flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0216 dis:Alpha Airside DD 1-5-7 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-020f flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0217 dis:Alpha Airside DD 1-5-7 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-020f his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0218 dis:Alpha Airside DD 1-5-7 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-020f his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0219 dis:Alpha Airside DD 1-5-7 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-020f heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-021a dis:Alpha Airside DD 1-5-7 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-020f his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-021b dis:Alpha Airside DD 1-5-7 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-020f heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-021c dis:Alpha Airside DD 1-5-7 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-020f his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-021d dis:Alpha Airside DD 1-5-8 airRef:@a-0051 dualDuct equip equipRef:@a-0051 hvac siteRef:@a-0000 thermostat vav --- id:@a-021e dis:Alpha Airside DD 1-5-8 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-021d his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-021f dis:Alpha Airside DD 1-5-8 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-021d flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0220 dis:Alpha Airside DD 1-5-8 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-021d flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0221 dis:Alpha Airside DD 1-5-8 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-021d his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0222 dis:Alpha Airside DD 1-5-8 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-021d his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0223 dis:Alpha Airside DD 1-5-8 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-021d flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0224 dis:Alpha Airside DD 1-5-8 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-021d flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0225 dis:Alpha Airside DD 1-5-8 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-021d his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0226 dis:Alpha Airside DD 1-5-8 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-021d his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0227 dis:Alpha Airside DD 1-5-8 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-021d heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0228 dis:Alpha Airside DD 1-5-8 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-021d his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0229 dis:Alpha Airside DD 1-5-8 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-021d heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-022a dis:Alpha Airside DD 1-5-8 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-021d his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-022b dis:Alpha Airside DD 1-5-9 airRef:@a-0051 dualDuct equip equipRef:@a-0051 hvac siteRef:@a-0000 thermostat vav --- id:@a-022c dis:Alpha Airside DD 1-5-9 Cold Deck Air Damper air cmd coldDeck cur custom:{description:"Clg Dmpr Pos. %"} damper equipRef:@a-022b his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-022d dis:Alpha Airside DD 1-5-9 Cold Deck Air Flow air coldDeck cur custom:{description:"Airflow sensor 2 (Cold)"} equipRef:@a-022b flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-022e dis:Alpha Airside DD 1-5-9 Cold Deck Air Flow Setpoint air coldDeck cur custom:{description:"Desired Airflow - Cold"} equipRef:@a-022b flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-022f dis:Alpha Airside DD 1-5-9 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-022b his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0230 dis:Alpha Airside DD 1-5-9 Hot Deck Air Damper air cmd cur custom:{description:"Htg Dmpr Cmnd 0-100"} damper equipRef:@a-022b his hotDeck kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0231 dis:Alpha Airside DD 1-5-9 Hot Deck Air Flow air cur custom:{description:"Airflow sensor 1 (Hot)"} equipRef:@a-022b flow his hotDeck kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0232 dis:Alpha Airside DD 1-5-9 Hot Deck Air Flow Setpoint air cur custom:{description:"Desired Airflow - Hot"} equipRef:@a-022b flow his hotDeck kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0233 dis:Alpha Airside DD 1-5-9 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-022b his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0234 dis:Alpha Airside DD 1-5-9 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-022b his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0235 dis:Alpha Airside DD 1-5-9 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-022b heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0236 dis:Alpha Airside DD 1-5-9 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-022b his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0237 dis:Alpha Airside DD 1-5-9 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-022b heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0238 dis:Alpha Airside DD 1-5-9 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-022b his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0239 dis:Alpha Airside EF-1 airRef:@a-0020 equip equipRef:@a-0020 fan hvac siteRef:@a-0000 --- id:@a-023a dis:Alpha Airside EF-1 Fan Status air cur custom:{description:"EF-1 Status"} equipRef:@a-0239 fan his hisMode:cov kind:Bool point run sensor siteRef:@a-0000 tz:Denver --- id:@a-023b dis:Alpha Airside EF-2 airRef:@a-0020 equip equipRef:@a-0020 fan hvac siteRef:@a-0000 --- id:@a-023c dis:Alpha Airside EF-2 Fan Status air cur custom:{description:"EF-2 Status"} equipRef:@a-023b fan his hisMode:cov kind:Bool point run sensor siteRef:@a-0000 tz:Denver --- id:@a-023d dis:Alpha Airside EF-3 airRef:@a-0020 equip equipRef:@a-0020 fan hvac siteRef:@a-0000 --- id:@a-023e dis:Alpha Airside EF-3 Fan Status air cur custom:{description:"EF-3 Status"} equipRef:@a-023d fan his hisMode:cov kind:Bool point run sensor siteRef:@a-0000 tz:Denver --- id:@a-023f dis:Alpha Airside EF-4 airRef:@a-0020 equip equipRef:@a-0020 fan hvac siteRef:@a-0000 --- id:@a-0240 dis:Alpha Airside EF-4 Fan Status air cur custom:{description:"EF-4 Status"} equipRef:@a-023f fan his hisMode:cov kind:Bool point run sensor siteRef:@a-0000 tz:Denver --- id:@a-0241 dis:Alpha Airside VAV 1-2-1 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0242 dis:Alpha Airside VAV 1-2-1 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0241 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0243 dis:Alpha Airside VAV 1-2-1 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0241 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0244 dis:Alpha Airside VAV 1-2-1 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0241 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0245 dis:Alpha Airside VAV 1-2-1 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0241 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0246 dis:Alpha Airside VAV 1-2-1 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0241 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0247 dis:Alpha Airside VAV 1-2-1 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0241 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0248 dis:Alpha Airside VAV 1-2-1 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0241 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0249 dis:Alpha Airside VAV 1-2-1 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0241 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-024a dis:Alpha Airside VAV 1-2-1 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0241 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-024b dis:Alpha Airside VAV 1-2-1 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0241 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-024c dis:Alpha Airside VAV 1-2-1 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0241 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-024d dis:Alpha Airside VAV 1-2-10 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-024e dis:Alpha Airside VAV 1-2-10 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-024d his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-024f dis:Alpha Airside VAV 1-2-10 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-024d flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0250 dis:Alpha Airside VAV 1-2-10 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-024d flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0251 dis:Alpha Airside VAV 1-2-10 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-024d his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0252 dis:Alpha Airside VAV 1-2-10 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-024d heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0253 dis:Alpha Airside VAV 1-2-10 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-024d his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0254 dis:Alpha Airside VAV 1-2-10 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-024d his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0255 dis:Alpha Airside VAV 1-2-10 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-024d heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0256 dis:Alpha Airside VAV 1-2-10 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-024d his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0257 dis:Alpha Airside VAV 1-2-10 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-024d heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0258 dis:Alpha Airside VAV 1-2-10 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-024d his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0259 dis:Alpha Airside VAV 1-2-11 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-025a dis:Alpha Airside VAV 1-2-11 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0259 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-025b dis:Alpha Airside VAV 1-2-11 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0259 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-025c dis:Alpha Airside VAV 1-2-11 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0259 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-025d dis:Alpha Airside VAV 1-2-11 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0259 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-025e dis:Alpha Airside VAV 1-2-11 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0259 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-025f dis:Alpha Airside VAV 1-2-11 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0259 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0260 dis:Alpha Airside VAV 1-2-11 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0259 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0261 dis:Alpha Airside VAV 1-2-11 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0259 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0262 dis:Alpha Airside VAV 1-2-11 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0259 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0263 dis:Alpha Airside VAV 1-2-11 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0259 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0264 dis:Alpha Airside VAV 1-2-11 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0259 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0265 dis:Alpha Airside VAV 1-2-12 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0266 dis:Alpha Airside VAV 1-2-12 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0265 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0267 dis:Alpha Airside VAV 1-2-12 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0265 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0268 dis:Alpha Airside VAV 1-2-12 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0265 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0269 dis:Alpha Airside VAV 1-2-12 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0265 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-026a dis:Alpha Airside VAV 1-2-12 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0265 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-026b dis:Alpha Airside VAV 1-2-12 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0265 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-026c dis:Alpha Airside VAV 1-2-12 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0265 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-026d dis:Alpha Airside VAV 1-2-12 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0265 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-026e dis:Alpha Airside VAV 1-2-12 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0265 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-026f dis:Alpha Airside VAV 1-2-12 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0265 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0270 dis:Alpha Airside VAV 1-2-12 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0265 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0271 dis:Alpha Airside VAV 1-2-13 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0272 dis:Alpha Airside VAV 1-2-13 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0271 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0273 dis:Alpha Airside VAV 1-2-13 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0271 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0274 dis:Alpha Airside VAV 1-2-13 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0271 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0275 dis:Alpha Airside VAV 1-2-13 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0271 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0276 dis:Alpha Airside VAV 1-2-13 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0271 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0277 dis:Alpha Airside VAV 1-2-13 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0271 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0278 dis:Alpha Airside VAV 1-2-13 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0271 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0279 dis:Alpha Airside VAV 1-2-13 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0271 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-027a dis:Alpha Airside VAV 1-2-13 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0271 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-027b dis:Alpha Airside VAV 1-2-13 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0271 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-027c dis:Alpha Airside VAV 1-2-13 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0271 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-027d dis:Alpha Airside VAV 1-2-14 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-027e dis:Alpha Airside VAV 1-2-14 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-027d his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-027f dis:Alpha Airside VAV 1-2-14 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-027d flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0280 dis:Alpha Airside VAV 1-2-14 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-027d flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0281 dis:Alpha Airside VAV 1-2-14 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-027d his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0282 dis:Alpha Airside VAV 1-2-14 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-027d heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0283 dis:Alpha Airside VAV 1-2-14 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-027d his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0284 dis:Alpha Airside VAV 1-2-14 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-027d his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0285 dis:Alpha Airside VAV 1-2-14 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-027d heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0286 dis:Alpha Airside VAV 1-2-14 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-027d his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0287 dis:Alpha Airside VAV 1-2-14 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-027d heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0288 dis:Alpha Airside VAV 1-2-14 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-027d his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0289 dis:Alpha Airside VAV 1-2-15 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-028a dis:Alpha Airside VAV 1-2-15 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0289 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-028b dis:Alpha Airside VAV 1-2-15 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0289 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-028c dis:Alpha Airside VAV 1-2-15 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0289 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-028d dis:Alpha Airside VAV 1-2-15 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0289 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-028e dis:Alpha Airside VAV 1-2-15 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0289 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-028f dis:Alpha Airside VAV 1-2-15 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0289 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0290 dis:Alpha Airside VAV 1-2-15 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0289 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0291 dis:Alpha Airside VAV 1-2-15 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0289 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0292 dis:Alpha Airside VAV 1-2-15 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0289 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0293 dis:Alpha Airside VAV 1-2-15 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0289 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0294 dis:Alpha Airside VAV 1-2-15 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0289 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0295 dis:Alpha Airside VAV 1-2-16 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0296 dis:Alpha Airside VAV 1-2-16 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0295 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0297 dis:Alpha Airside VAV 1-2-16 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0295 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0298 dis:Alpha Airside VAV 1-2-16 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0295 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0299 dis:Alpha Airside VAV 1-2-16 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0295 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-029a dis:Alpha Airside VAV 1-2-16 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0295 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-029b dis:Alpha Airside VAV 1-2-16 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0295 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-029c dis:Alpha Airside VAV 1-2-16 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0295 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-029d dis:Alpha Airside VAV 1-2-16 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0295 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-029e dis:Alpha Airside VAV 1-2-16 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0295 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-029f dis:Alpha Airside VAV 1-2-16 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0295 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-02a0 dis:Alpha Airside VAV 1-2-16 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0295 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-02a1 dis:Alpha Airside VAV 1-2-17 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-02a2 dis:Alpha Airside VAV 1-2-17 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-02a1 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-02a3 dis:Alpha Airside VAV 1-2-17 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-02a1 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-02a4 dis:Alpha Airside VAV 1-2-17 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-02a1 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-02a5 dis:Alpha Airside VAV 1-2-17 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-02a1 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-02a6 dis:Alpha Airside VAV 1-2-17 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-02a1 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-02a7 dis:Alpha Airside VAV 1-2-17 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-02a1 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-02a8 dis:Alpha Airside VAV 1-2-17 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-02a1 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-02a9 dis:Alpha Airside VAV 1-2-17 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-02a1 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-02aa dis:Alpha Airside VAV 1-2-17 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-02a1 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-02ab dis:Alpha Airside VAV 1-2-17 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-02a1 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-02ac dis:Alpha Airside VAV 1-2-17 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-02a1 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-02ad dis:Alpha Airside VAV 1-2-18 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-02ae dis:Alpha Airside VAV 1-2-18 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-02ad his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-02af dis:Alpha Airside VAV 1-2-18 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-02ad flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-02b0 dis:Alpha Airside VAV 1-2-18 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-02ad flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-02b1 dis:Alpha Airside VAV 1-2-18 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-02ad his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-02b2 dis:Alpha Airside VAV 1-2-18 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-02ad heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-02b3 dis:Alpha Airside VAV 1-2-18 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-02ad his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-02b4 dis:Alpha Airside VAV 1-2-18 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-02ad his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-02b5 dis:Alpha Airside VAV 1-2-18 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-02ad heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-02b6 dis:Alpha Airside VAV 1-2-18 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-02ad his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-02b7 dis:Alpha Airside VAV 1-2-18 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-02ad heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-02b8 dis:Alpha Airside VAV 1-2-18 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-02ad his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-02b9 dis:Alpha Airside VAV 1-2-19 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-02ba dis:Alpha Airside VAV 1-2-19 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-02b9 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-02bb dis:Alpha Airside VAV 1-2-19 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-02b9 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-02bc dis:Alpha Airside VAV 1-2-19 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-02b9 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-02bd dis:Alpha Airside VAV 1-2-19 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-02b9 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-02be dis:Alpha Airside VAV 1-2-19 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-02b9 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-02bf dis:Alpha Airside VAV 1-2-19 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-02b9 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-02c0 dis:Alpha Airside VAV 1-2-19 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-02b9 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-02c1 dis:Alpha Airside VAV 1-2-19 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-02b9 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-02c2 dis:Alpha Airside VAV 1-2-19 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-02b9 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-02c3 dis:Alpha Airside VAV 1-2-19 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-02b9 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-02c4 dis:Alpha Airside VAV 1-2-19 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-02b9 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-02c5 dis:Alpha Airside VAV 1-2-20 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-02c6 dis:Alpha Airside VAV 1-2-20 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-02c5 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-02c7 dis:Alpha Airside VAV 1-2-20 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-02c5 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-02c8 dis:Alpha Airside VAV 1-2-20 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-02c5 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-02c9 dis:Alpha Airside VAV 1-2-20 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-02c5 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-02ca dis:Alpha Airside VAV 1-2-20 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-02c5 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-02cb dis:Alpha Airside VAV 1-2-20 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-02c5 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-02cc dis:Alpha Airside VAV 1-2-20 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-02c5 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-02cd dis:Alpha Airside VAV 1-2-20 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-02c5 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-02ce dis:Alpha Airside VAV 1-2-20 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-02c5 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-02cf dis:Alpha Airside VAV 1-2-20 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-02c5 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-02d0 dis:Alpha Airside VAV 1-2-20 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-02c5 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-02d1 dis:Alpha Airside VAV 1-2-21 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-02d2 dis:Alpha Airside VAV 1-2-21 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-02d1 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-02d3 dis:Alpha Airside VAV 1-2-21 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-02d1 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-02d4 dis:Alpha Airside VAV 1-2-21 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-02d1 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-02d5 dis:Alpha Airside VAV 1-2-21 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-02d1 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-02d6 dis:Alpha Airside VAV 1-2-21 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-02d1 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-02d7 dis:Alpha Airside VAV 1-2-21 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-02d1 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-02d8 dis:Alpha Airside VAV 1-2-21 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-02d1 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-02d9 dis:Alpha Airside VAV 1-2-21 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-02d1 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-02da dis:Alpha Airside VAV 1-2-21 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-02d1 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-02db dis:Alpha Airside VAV 1-2-21 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-02d1 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-02dc dis:Alpha Airside VAV 1-2-21 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-02d1 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-02dd dis:Alpha Airside VAV 1-2-22 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-02de dis:Alpha Airside VAV 1-2-22 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-02dd his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-02df dis:Alpha Airside VAV 1-2-22 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-02dd flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-02e0 dis:Alpha Airside VAV 1-2-22 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-02dd flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-02e1 dis:Alpha Airside VAV 1-2-22 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-02dd his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-02e2 dis:Alpha Airside VAV 1-2-22 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-02dd heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-02e3 dis:Alpha Airside VAV 1-2-22 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-02dd his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-02e4 dis:Alpha Airside VAV 1-2-22 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-02dd his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-02e5 dis:Alpha Airside VAV 1-2-22 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-02dd heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-02e6 dis:Alpha Airside VAV 1-2-22 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-02dd his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-02e7 dis:Alpha Airside VAV 1-2-22 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-02dd heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-02e8 dis:Alpha Airside VAV 1-2-22 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-02dd his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-02e9 dis:Alpha Airside VAV 1-2-23 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-02ea dis:Alpha Airside VAV 1-2-23 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-02e9 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-02eb dis:Alpha Airside VAV 1-2-23 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-02e9 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-02ec dis:Alpha Airside VAV 1-2-23 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-02e9 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-02ed dis:Alpha Airside VAV 1-2-23 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-02e9 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-02ee dis:Alpha Airside VAV 1-2-23 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-02e9 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-02ef dis:Alpha Airside VAV 1-2-23 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-02e9 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-02f0 dis:Alpha Airside VAV 1-2-23 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-02e9 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-02f1 dis:Alpha Airside VAV 1-2-23 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-02e9 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-02f2 dis:Alpha Airside VAV 1-2-23 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-02e9 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-02f3 dis:Alpha Airside VAV 1-2-23 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-02e9 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-02f4 dis:Alpha Airside VAV 1-2-23 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-02e9 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-02f5 dis:Alpha Airside VAV 1-2-25 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-02f6 dis:Alpha Airside VAV 1-2-25 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-02f5 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-02f7 dis:Alpha Airside VAV 1-2-25 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-02f5 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-02f8 dis:Alpha Airside VAV 1-2-25 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-02f5 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-02f9 dis:Alpha Airside VAV 1-2-25 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-02f5 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-02fa dis:Alpha Airside VAV 1-2-25 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-02f5 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-02fb dis:Alpha Airside VAV 1-2-25 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-02f5 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-02fc dis:Alpha Airside VAV 1-2-25 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-02f5 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-02fd dis:Alpha Airside VAV 1-2-25 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-02f5 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-02fe dis:Alpha Airside VAV 1-2-25 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-02f5 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-02ff dis:Alpha Airside VAV 1-2-25 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-02f5 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0300 dis:Alpha Airside VAV 1-2-25 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-02f5 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0301 dis:Alpha Airside VAV 1-2-26 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0302 dis:Alpha Airside VAV 1-2-26 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0301 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0303 dis:Alpha Airside VAV 1-2-26 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0301 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0304 dis:Alpha Airside VAV 1-2-26 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0301 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0305 dis:Alpha Airside VAV 1-2-26 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0301 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0306 dis:Alpha Airside VAV 1-2-26 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0301 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0307 dis:Alpha Airside VAV 1-2-26 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0301 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0308 dis:Alpha Airside VAV 1-2-26 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0301 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0309 dis:Alpha Airside VAV 1-2-26 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0301 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-030a dis:Alpha Airside VAV 1-2-26 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0301 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-030b dis:Alpha Airside VAV 1-2-26 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0301 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-030c dis:Alpha Airside VAV 1-2-26 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0301 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-030d dis:Alpha Airside VAV 1-2-27 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-030e dis:Alpha Airside VAV 1-2-27 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-030d his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-030f dis:Alpha Airside VAV 1-2-27 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-030d flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0310 dis:Alpha Airside VAV 1-2-27 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-030d flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0311 dis:Alpha Airside VAV 1-2-27 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-030d his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0312 dis:Alpha Airside VAV 1-2-27 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-030d heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0313 dis:Alpha Airside VAV 1-2-27 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-030d his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0314 dis:Alpha Airside VAV 1-2-27 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-030d his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0315 dis:Alpha Airside VAV 1-2-27 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-030d heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0316 dis:Alpha Airside VAV 1-2-27 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-030d his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0317 dis:Alpha Airside VAV 1-2-27 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-030d heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0318 dis:Alpha Airside VAV 1-2-27 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-030d his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0319 dis:Alpha Airside VAV 1-2-28 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-031a dis:Alpha Airside VAV 1-2-28 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0319 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-031b dis:Alpha Airside VAV 1-2-28 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0319 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-031c dis:Alpha Airside VAV 1-2-28 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0319 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-031d dis:Alpha Airside VAV 1-2-28 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0319 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-031e dis:Alpha Airside VAV 1-2-28 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0319 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-031f dis:Alpha Airside VAV 1-2-28 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0319 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0320 dis:Alpha Airside VAV 1-2-28 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0319 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0321 dis:Alpha Airside VAV 1-2-28 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0319 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0322 dis:Alpha Airside VAV 1-2-28 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0319 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0323 dis:Alpha Airside VAV 1-2-28 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0319 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0324 dis:Alpha Airside VAV 1-2-28 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0319 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0325 dis:Alpha Airside VAV 1-2-29 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0326 dis:Alpha Airside VAV 1-2-29 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0325 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0327 dis:Alpha Airside VAV 1-2-29 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0325 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0328 dis:Alpha Airside VAV 1-2-29 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0325 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0329 dis:Alpha Airside VAV 1-2-29 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0325 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-032a dis:Alpha Airside VAV 1-2-29 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0325 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-032b dis:Alpha Airside VAV 1-2-29 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0325 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-032c dis:Alpha Airside VAV 1-2-29 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0325 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-032d dis:Alpha Airside VAV 1-2-29 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0325 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-032e dis:Alpha Airside VAV 1-2-29 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0325 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-032f dis:Alpha Airside VAV 1-2-29 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0325 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0330 dis:Alpha Airside VAV 1-2-29 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0325 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0331 dis:Alpha Airside VAV 1-2-3 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0332 dis:Alpha Airside VAV 1-2-3 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0331 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0333 dis:Alpha Airside VAV 1-2-3 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0331 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0334 dis:Alpha Airside VAV 1-2-3 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0331 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0335 dis:Alpha Airside VAV 1-2-3 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0331 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0336 dis:Alpha Airside VAV 1-2-3 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0331 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0337 dis:Alpha Airside VAV 1-2-3 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0331 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0338 dis:Alpha Airside VAV 1-2-3 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0331 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0339 dis:Alpha Airside VAV 1-2-3 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0331 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-033a dis:Alpha Airside VAV 1-2-3 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0331 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-033b dis:Alpha Airside VAV 1-2-3 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0331 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-033c dis:Alpha Airside VAV 1-2-3 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0331 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-033d dis:Alpha Airside VAV 1-2-30 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-033e dis:Alpha Airside VAV 1-2-30 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-033d his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-033f dis:Alpha Airside VAV 1-2-30 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-033d flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0340 dis:Alpha Airside VAV 1-2-30 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-033d flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0341 dis:Alpha Airside VAV 1-2-30 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-033d his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0342 dis:Alpha Airside VAV 1-2-30 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-033d heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0343 dis:Alpha Airside VAV 1-2-30 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-033d his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0344 dis:Alpha Airside VAV 1-2-30 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-033d his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0345 dis:Alpha Airside VAV 1-2-30 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-033d heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0346 dis:Alpha Airside VAV 1-2-30 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-033d his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0347 dis:Alpha Airside VAV 1-2-30 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-033d heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0348 dis:Alpha Airside VAV 1-2-30 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-033d his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0349 dis:Alpha Airside VAV 1-2-31 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-034a dis:Alpha Airside VAV 1-2-31 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0349 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-034b dis:Alpha Airside VAV 1-2-31 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0349 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-034c dis:Alpha Airside VAV 1-2-31 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0349 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-034d dis:Alpha Airside VAV 1-2-31 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0349 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-034e dis:Alpha Airside VAV 1-2-31 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0349 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-034f dis:Alpha Airside VAV 1-2-31 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0349 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0350 dis:Alpha Airside VAV 1-2-31 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0349 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0351 dis:Alpha Airside VAV 1-2-31 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0349 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0352 dis:Alpha Airside VAV 1-2-31 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0349 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0353 dis:Alpha Airside VAV 1-2-31 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0349 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0354 dis:Alpha Airside VAV 1-2-31 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0349 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0355 dis:Alpha Airside VAV 1-2-32 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0356 dis:Alpha Airside VAV 1-2-32 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0355 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0357 dis:Alpha Airside VAV 1-2-32 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0355 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0358 dis:Alpha Airside VAV 1-2-32 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0355 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0359 dis:Alpha Airside VAV 1-2-32 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0355 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-035a dis:Alpha Airside VAV 1-2-32 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0355 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-035b dis:Alpha Airside VAV 1-2-32 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0355 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-035c dis:Alpha Airside VAV 1-2-32 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0355 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-035d dis:Alpha Airside VAV 1-2-32 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0355 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-035e dis:Alpha Airside VAV 1-2-32 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0355 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-035f dis:Alpha Airside VAV 1-2-32 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0355 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0360 dis:Alpha Airside VAV 1-2-32 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0355 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0361 dis:Alpha Airside VAV 1-2-33 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0362 dis:Alpha Airside VAV 1-2-33 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0361 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0363 dis:Alpha Airside VAV 1-2-33 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0361 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0364 dis:Alpha Airside VAV 1-2-33 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0361 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0365 dis:Alpha Airside VAV 1-2-33 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0361 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0366 dis:Alpha Airside VAV 1-2-33 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0361 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0367 dis:Alpha Airside VAV 1-2-33 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0361 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0368 dis:Alpha Airside VAV 1-2-33 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0361 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0369 dis:Alpha Airside VAV 1-2-33 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0361 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-036a dis:Alpha Airside VAV 1-2-33 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0361 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-036b dis:Alpha Airside VAV 1-2-33 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0361 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-036c dis:Alpha Airside VAV 1-2-33 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0361 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-036d dis:Alpha Airside VAV 1-2-34 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-036e dis:Alpha Airside VAV 1-2-34 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-036d his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-036f dis:Alpha Airside VAV 1-2-34 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-036d flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0370 dis:Alpha Airside VAV 1-2-34 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-036d flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0371 dis:Alpha Airside VAV 1-2-34 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-036d his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0372 dis:Alpha Airside VAV 1-2-34 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-036d heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0373 dis:Alpha Airside VAV 1-2-34 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-036d his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0374 dis:Alpha Airside VAV 1-2-34 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-036d his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0375 dis:Alpha Airside VAV 1-2-34 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-036d heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0376 dis:Alpha Airside VAV 1-2-34 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-036d his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0377 dis:Alpha Airside VAV 1-2-34 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-036d heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0378 dis:Alpha Airside VAV 1-2-34 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-036d his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0379 dis:Alpha Airside VAV 1-2-35 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-037a dis:Alpha Airside VAV 1-2-35 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0379 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-037b dis:Alpha Airside VAV 1-2-35 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0379 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-037c dis:Alpha Airside VAV 1-2-35 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0379 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-037d dis:Alpha Airside VAV 1-2-35 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0379 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-037e dis:Alpha Airside VAV 1-2-35 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0379 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-037f dis:Alpha Airside VAV 1-2-35 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0379 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0380 dis:Alpha Airside VAV 1-2-35 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0379 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0381 dis:Alpha Airside VAV 1-2-35 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0379 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0382 dis:Alpha Airside VAV 1-2-35 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0379 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0383 dis:Alpha Airside VAV 1-2-35 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0379 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0384 dis:Alpha Airside VAV 1-2-35 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0379 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0385 dis:Alpha Airside VAV 1-2-36 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0386 dis:Alpha Airside VAV 1-2-36 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0385 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0387 dis:Alpha Airside VAV 1-2-36 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0385 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0388 dis:Alpha Airside VAV 1-2-36 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0385 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0389 dis:Alpha Airside VAV 1-2-36 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0385 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-038a dis:Alpha Airside VAV 1-2-36 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0385 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-038b dis:Alpha Airside VAV 1-2-36 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0385 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-038c dis:Alpha Airside VAV 1-2-36 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0385 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-038d dis:Alpha Airside VAV 1-2-36 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0385 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-038e dis:Alpha Airside VAV 1-2-36 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0385 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-038f dis:Alpha Airside VAV 1-2-36 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0385 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0390 dis:Alpha Airside VAV 1-2-36 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0385 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0391 dis:Alpha Airside VAV 1-2-37 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0392 dis:Alpha Airside VAV 1-2-37 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0391 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0393 dis:Alpha Airside VAV 1-2-37 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0391 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0394 dis:Alpha Airside VAV 1-2-37 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0391 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0395 dis:Alpha Airside VAV 1-2-37 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0391 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0396 dis:Alpha Airside VAV 1-2-37 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0391 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0397 dis:Alpha Airside VAV 1-2-37 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0391 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0398 dis:Alpha Airside VAV 1-2-37 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0391 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0399 dis:Alpha Airside VAV 1-2-37 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0391 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-039a dis:Alpha Airside VAV 1-2-37 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0391 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-039b dis:Alpha Airside VAV 1-2-37 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0391 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-039c dis:Alpha Airside VAV 1-2-37 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0391 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-039d dis:Alpha Airside VAV 1-2-38 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-039e dis:Alpha Airside VAV 1-2-38 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-039d his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-039f dis:Alpha Airside VAV 1-2-38 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-039d flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-03a0 dis:Alpha Airside VAV 1-2-38 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-039d flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-03a1 dis:Alpha Airside VAV 1-2-38 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-039d his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-03a2 dis:Alpha Airside VAV 1-2-38 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-039d heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-03a3 dis:Alpha Airside VAV 1-2-38 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-039d his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-03a4 dis:Alpha Airside VAV 1-2-38 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-039d his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-03a5 dis:Alpha Airside VAV 1-2-38 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-039d heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-03a6 dis:Alpha Airside VAV 1-2-38 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-039d his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-03a7 dis:Alpha Airside VAV 1-2-38 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-039d heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-03a8 dis:Alpha Airside VAV 1-2-38 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-039d his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-03a9 dis:Alpha Airside VAV 1-2-4 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-03aa dis:Alpha Airside VAV 1-2-4 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-03a9 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-03ab dis:Alpha Airside VAV 1-2-4 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-03a9 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-03ac dis:Alpha Airside VAV 1-2-4 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-03a9 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-03ad dis:Alpha Airside VAV 1-2-4 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-03a9 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-03ae dis:Alpha Airside VAV 1-2-4 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-03a9 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-03af dis:Alpha Airside VAV 1-2-4 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-03a9 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-03b0 dis:Alpha Airside VAV 1-2-4 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-03a9 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-03b1 dis:Alpha Airside VAV 1-2-4 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-03a9 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-03b2 dis:Alpha Airside VAV 1-2-4 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-03a9 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-03b3 dis:Alpha Airside VAV 1-2-4 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-03a9 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-03b4 dis:Alpha Airside VAV 1-2-4 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-03a9 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-03b5 dis:Alpha Airside VAV 1-2-40 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-03b6 dis:Alpha Airside VAV 1-2-40 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-03b5 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-03b7 dis:Alpha Airside VAV 1-2-40 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-03b5 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-03b8 dis:Alpha Airside VAV 1-2-40 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-03b5 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-03b9 dis:Alpha Airside VAV 1-2-40 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-03b5 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-03ba dis:Alpha Airside VAV 1-2-40 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-03b5 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-03bb dis:Alpha Airside VAV 1-2-40 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-03b5 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-03bc dis:Alpha Airside VAV 1-2-40 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-03b5 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-03bd dis:Alpha Airside VAV 1-2-40 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-03b5 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-03be dis:Alpha Airside VAV 1-2-40 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-03b5 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-03bf dis:Alpha Airside VAV 1-2-40 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-03b5 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-03c0 dis:Alpha Airside VAV 1-2-40 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-03b5 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-03c1 dis:Alpha Airside VAV 1-2-41 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-03c2 dis:Alpha Airside VAV 1-2-41 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-03c1 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-03c3 dis:Alpha Airside VAV 1-2-41 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-03c1 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-03c4 dis:Alpha Airside VAV 1-2-41 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-03c1 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-03c5 dis:Alpha Airside VAV 1-2-41 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-03c1 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-03c6 dis:Alpha Airside VAV 1-2-41 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-03c1 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-03c7 dis:Alpha Airside VAV 1-2-41 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-03c1 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-03c8 dis:Alpha Airside VAV 1-2-41 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-03c1 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-03c9 dis:Alpha Airside VAV 1-2-41 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-03c1 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-03ca dis:Alpha Airside VAV 1-2-41 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-03c1 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-03cb dis:Alpha Airside VAV 1-2-41 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-03c1 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-03cc dis:Alpha Airside VAV 1-2-41 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-03c1 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-03cd dis:Alpha Airside VAV 1-2-42 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-03ce dis:Alpha Airside VAV 1-2-42 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-03cd his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-03cf dis:Alpha Airside VAV 1-2-42 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-03cd flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-03d0 dis:Alpha Airside VAV 1-2-42 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-03cd flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-03d1 dis:Alpha Airside VAV 1-2-42 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-03cd his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-03d2 dis:Alpha Airside VAV 1-2-42 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-03cd heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-03d3 dis:Alpha Airside VAV 1-2-42 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-03cd his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-03d4 dis:Alpha Airside VAV 1-2-42 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-03cd his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-03d5 dis:Alpha Airside VAV 1-2-42 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-03cd heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-03d6 dis:Alpha Airside VAV 1-2-42 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-03cd his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-03d7 dis:Alpha Airside VAV 1-2-42 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-03cd heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-03d8 dis:Alpha Airside VAV 1-2-42 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-03cd his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-03d9 dis:Alpha Airside VAV 1-2-43 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-03da dis:Alpha Airside VAV 1-2-43 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-03d9 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-03db dis:Alpha Airside VAV 1-2-43 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-03d9 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-03dc dis:Alpha Airside VAV 1-2-43 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-03d9 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-03dd dis:Alpha Airside VAV 1-2-43 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-03d9 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-03de dis:Alpha Airside VAV 1-2-43 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-03d9 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-03df dis:Alpha Airside VAV 1-2-43 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-03d9 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-03e0 dis:Alpha Airside VAV 1-2-43 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-03d9 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-03e1 dis:Alpha Airside VAV 1-2-43 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-03d9 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-03e2 dis:Alpha Airside VAV 1-2-43 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-03d9 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-03e3 dis:Alpha Airside VAV 1-2-43 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-03d9 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-03e4 dis:Alpha Airside VAV 1-2-43 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-03d9 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-03e5 dis:Alpha Airside VAV 1-2-44 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-03e6 dis:Alpha Airside VAV 1-2-44 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-03e5 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-03e7 dis:Alpha Airside VAV 1-2-44 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-03e5 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-03e8 dis:Alpha Airside VAV 1-2-44 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-03e5 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-03e9 dis:Alpha Airside VAV 1-2-44 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-03e5 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-03ea dis:Alpha Airside VAV 1-2-44 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-03e5 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-03eb dis:Alpha Airside VAV 1-2-44 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-03e5 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-03ec dis:Alpha Airside VAV 1-2-44 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-03e5 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-03ed dis:Alpha Airside VAV 1-2-44 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-03e5 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-03ee dis:Alpha Airside VAV 1-2-44 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-03e5 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-03ef dis:Alpha Airside VAV 1-2-44 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-03e5 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-03f0 dis:Alpha Airside VAV 1-2-44 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-03e5 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-03f1 dis:Alpha Airside VAV 1-2-45 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-03f2 dis:Alpha Airside VAV 1-2-45 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-03f1 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-03f3 dis:Alpha Airside VAV 1-2-45 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-03f1 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-03f4 dis:Alpha Airside VAV 1-2-45 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-03f1 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-03f5 dis:Alpha Airside VAV 1-2-45 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-03f1 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-03f6 dis:Alpha Airside VAV 1-2-45 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-03f1 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-03f7 dis:Alpha Airside VAV 1-2-45 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-03f1 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-03f8 dis:Alpha Airside VAV 1-2-45 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-03f1 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-03f9 dis:Alpha Airside VAV 1-2-45 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-03f1 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-03fa dis:Alpha Airside VAV 1-2-45 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-03f1 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-03fb dis:Alpha Airside VAV 1-2-45 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-03f1 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-03fc dis:Alpha Airside VAV 1-2-45 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-03f1 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-03fd dis:Alpha Airside VAV 1-2-46 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-03fe dis:Alpha Airside VAV 1-2-46 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-03fd his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-03ff dis:Alpha Airside VAV 1-2-46 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-03fd flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0400 dis:Alpha Airside VAV 1-2-46 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-03fd flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0401 dis:Alpha Airside VAV 1-2-46 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-03fd his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0402 dis:Alpha Airside VAV 1-2-46 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-03fd heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0403 dis:Alpha Airside VAV 1-2-46 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-03fd his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0404 dis:Alpha Airside VAV 1-2-46 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-03fd his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0405 dis:Alpha Airside VAV 1-2-46 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-03fd heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0406 dis:Alpha Airside VAV 1-2-46 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-03fd his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0407 dis:Alpha Airside VAV 1-2-46 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-03fd heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0408 dis:Alpha Airside VAV 1-2-46 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-03fd his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0409 dis:Alpha Airside VAV 1-2-47 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-040a dis:Alpha Airside VAV 1-2-47 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0409 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-040b dis:Alpha Airside VAV 1-2-47 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0409 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-040c dis:Alpha Airside VAV 1-2-47 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0409 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-040d dis:Alpha Airside VAV 1-2-47 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0409 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-040e dis:Alpha Airside VAV 1-2-47 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0409 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-040f dis:Alpha Airside VAV 1-2-47 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0409 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0410 dis:Alpha Airside VAV 1-2-47 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0409 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0411 dis:Alpha Airside VAV 1-2-47 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0409 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0412 dis:Alpha Airside VAV 1-2-47 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0409 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0413 dis:Alpha Airside VAV 1-2-47 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0409 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0414 dis:Alpha Airside VAV 1-2-47 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0409 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0415 dis:Alpha Airside VAV 1-2-48 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0416 dis:Alpha Airside VAV 1-2-48 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0415 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0417 dis:Alpha Airside VAV 1-2-48 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0415 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0418 dis:Alpha Airside VAV 1-2-48 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0415 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0419 dis:Alpha Airside VAV 1-2-48 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0415 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-041a dis:Alpha Airside VAV 1-2-48 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0415 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-041b dis:Alpha Airside VAV 1-2-48 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0415 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-041c dis:Alpha Airside VAV 1-2-48 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0415 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-041d dis:Alpha Airside VAV 1-2-48 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0415 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-041e dis:Alpha Airside VAV 1-2-48 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0415 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-041f dis:Alpha Airside VAV 1-2-48 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0415 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0420 dis:Alpha Airside VAV 1-2-48 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0415 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0421 dis:Alpha Airside VAV 1-2-5 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0422 dis:Alpha Airside VAV 1-2-5 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0421 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0423 dis:Alpha Airside VAV 1-2-5 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0421 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0424 dis:Alpha Airside VAV 1-2-5 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0421 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0425 dis:Alpha Airside VAV 1-2-5 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0421 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0426 dis:Alpha Airside VAV 1-2-5 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0421 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0427 dis:Alpha Airside VAV 1-2-5 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0421 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0428 dis:Alpha Airside VAV 1-2-5 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0421 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0429 dis:Alpha Airside VAV 1-2-5 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0421 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-042a dis:Alpha Airside VAV 1-2-5 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0421 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-042b dis:Alpha Airside VAV 1-2-5 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0421 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-042c dis:Alpha Airside VAV 1-2-5 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0421 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-042d dis:Alpha Airside VAV 1-2-50 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-042e dis:Alpha Airside VAV 1-2-50 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-042d his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-042f dis:Alpha Airside VAV 1-2-50 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-042d flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0430 dis:Alpha Airside VAV 1-2-50 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-042d flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0431 dis:Alpha Airside VAV 1-2-50 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-042d his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0432 dis:Alpha Airside VAV 1-2-50 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-042d heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0433 dis:Alpha Airside VAV 1-2-50 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-042d his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0434 dis:Alpha Airside VAV 1-2-50 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-042d his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0435 dis:Alpha Airside VAV 1-2-50 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-042d heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0436 dis:Alpha Airside VAV 1-2-50 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-042d his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0437 dis:Alpha Airside VAV 1-2-50 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-042d heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0438 dis:Alpha Airside VAV 1-2-50 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-042d his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0439 dis:Alpha Airside VAV 1-2-51 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-043a dis:Alpha Airside VAV 1-2-51 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0439 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-043b dis:Alpha Airside VAV 1-2-51 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0439 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-043c dis:Alpha Airside VAV 1-2-51 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0439 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-043d dis:Alpha Airside VAV 1-2-51 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0439 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-043e dis:Alpha Airside VAV 1-2-51 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0439 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-043f dis:Alpha Airside VAV 1-2-51 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0439 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0440 dis:Alpha Airside VAV 1-2-51 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0439 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0441 dis:Alpha Airside VAV 1-2-51 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0439 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0442 dis:Alpha Airside VAV 1-2-51 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0439 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0443 dis:Alpha Airside VAV 1-2-51 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0439 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0444 dis:Alpha Airside VAV 1-2-51 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0439 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0445 dis:Alpha Airside VAV 1-2-52 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0446 dis:Alpha Airside VAV 1-2-52 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0445 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0447 dis:Alpha Airside VAV 1-2-52 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0445 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0448 dis:Alpha Airside VAV 1-2-52 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0445 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0449 dis:Alpha Airside VAV 1-2-52 Discharge Air Temp air cur discharge equipRef:@a-0445 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-044a dis:Alpha Airside VAV 1-2-52 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0445 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-044b dis:Alpha Airside VAV 1-2-52 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0445 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-044c dis:Alpha Airside VAV 1-2-52 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0445 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-044d dis:Alpha Airside VAV 1-2-52 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0445 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-044e dis:Alpha Airside VAV 1-2-52 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0445 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-044f dis:Alpha Airside VAV 1-2-52 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0445 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0450 dis:Alpha Airside VAV 1-2-53 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0451 dis:Alpha Airside VAV 1-2-53 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0450 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0452 dis:Alpha Airside VAV 1-2-53 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0450 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0453 dis:Alpha Airside VAV 1-2-53 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0450 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0454 dis:Alpha Airside VAV 1-2-53 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0450 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0455 dis:Alpha Airside VAV 1-2-53 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0450 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0456 dis:Alpha Airside VAV 1-2-53 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0450 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0457 dis:Alpha Airside VAV 1-2-53 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0450 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0458 dis:Alpha Airside VAV 1-2-53 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0450 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0459 dis:Alpha Airside VAV 1-2-53 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0450 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-045a dis:Alpha Airside VAV 1-2-53 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0450 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-045b dis:Alpha Airside VAV 1-2-53 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0450 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-045c dis:Alpha Airside VAV 1-2-55 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-045d dis:Alpha Airside VAV 1-2-55 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-045c his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-045e dis:Alpha Airside VAV 1-2-55 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-045c flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-045f dis:Alpha Airside VAV 1-2-55 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-045c flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0460 dis:Alpha Airside VAV 1-2-55 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-045c his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0461 dis:Alpha Airside VAV 1-2-55 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-045c heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0462 dis:Alpha Airside VAV 1-2-55 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-045c his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0463 dis:Alpha Airside VAV 1-2-55 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-045c his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0464 dis:Alpha Airside VAV 1-2-55 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-045c heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0465 dis:Alpha Airside VAV 1-2-55 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-045c his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0466 dis:Alpha Airside VAV 1-2-55 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-045c heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0467 dis:Alpha Airside VAV 1-2-55 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-045c his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0468 dis:Alpha Airside VAV 1-2-56 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0469 dis:Alpha Airside VAV 1-2-56 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0468 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-046a dis:Alpha Airside VAV 1-2-56 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0468 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-046b dis:Alpha Airside VAV 1-2-56 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0468 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-046c dis:Alpha Airside VAV 1-2-56 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0468 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-046d dis:Alpha Airside VAV 1-2-56 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0468 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-046e dis:Alpha Airside VAV 1-2-56 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0468 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-046f dis:Alpha Airside VAV 1-2-56 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0468 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0470 dis:Alpha Airside VAV 1-2-56 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0468 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0471 dis:Alpha Airside VAV 1-2-56 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0468 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0472 dis:Alpha Airside VAV 1-2-56 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0468 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0473 dis:Alpha Airside VAV 1-2-56 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0468 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0474 dis:Alpha Airside VAV 1-2-58 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0475 dis:Alpha Airside VAV 1-2-58 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0474 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0476 dis:Alpha Airside VAV 1-2-58 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0474 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0477 dis:Alpha Airside VAV 1-2-58 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0474 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0478 dis:Alpha Airside VAV 1-2-58 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0474 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0479 dis:Alpha Airside VAV 1-2-58 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0474 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-047a dis:Alpha Airside VAV 1-2-58 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0474 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-047b dis:Alpha Airside VAV 1-2-58 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0474 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-047c dis:Alpha Airside VAV 1-2-58 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0474 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-047d dis:Alpha Airside VAV 1-2-58 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0474 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-047e dis:Alpha Airside VAV 1-2-58 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0474 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-047f dis:Alpha Airside VAV 1-2-58 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0474 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0480 dis:Alpha Airside VAV 1-2-59 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0481 dis:Alpha Airside VAV 1-2-59 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0480 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0482 dis:Alpha Airside VAV 1-2-59 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0480 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0483 dis:Alpha Airside VAV 1-2-59 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0480 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0484 dis:Alpha Airside VAV 1-2-59 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0480 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0485 dis:Alpha Airside VAV 1-2-59 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0480 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0486 dis:Alpha Airside VAV 1-2-59 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0480 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0487 dis:Alpha Airside VAV 1-2-59 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0480 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0488 dis:Alpha Airside VAV 1-2-59 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0480 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0489 dis:Alpha Airside VAV 1-2-59 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0480 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-048a dis:Alpha Airside VAV 1-2-59 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0480 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-048b dis:Alpha Airside VAV 1-2-59 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0480 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-048c dis:Alpha Airside VAV 1-2-6 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-048d dis:Alpha Airside VAV 1-2-6 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-048c his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-048e dis:Alpha Airside VAV 1-2-6 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-048c flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-048f dis:Alpha Airside VAV 1-2-6 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-048c flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0490 dis:Alpha Airside VAV 1-2-6 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-048c his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0491 dis:Alpha Airside VAV 1-2-6 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-048c heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0492 dis:Alpha Airside VAV 1-2-6 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-048c his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0493 dis:Alpha Airside VAV 1-2-6 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-048c his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0494 dis:Alpha Airside VAV 1-2-6 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-048c heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0495 dis:Alpha Airside VAV 1-2-6 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-048c his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0496 dis:Alpha Airside VAV 1-2-6 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-048c heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0497 dis:Alpha Airside VAV 1-2-6 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-048c his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0498 dis:Alpha Airside VAV 1-2-61 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0499 dis:Alpha Airside VAV 1-2-61 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0498 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-049a dis:Alpha Airside VAV 1-2-61 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0498 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-049b dis:Alpha Airside VAV 1-2-61 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0498 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-049c dis:Alpha Airside VAV 1-2-61 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0498 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-049d dis:Alpha Airside VAV 1-2-61 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0498 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-049e dis:Alpha Airside VAV 1-2-61 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0498 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-049f dis:Alpha Airside VAV 1-2-61 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0498 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-04a0 dis:Alpha Airside VAV 1-2-61 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0498 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-04a1 dis:Alpha Airside VAV 1-2-61 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0498 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-04a2 dis:Alpha Airside VAV 1-2-61 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0498 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-04a3 dis:Alpha Airside VAV 1-2-61 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0498 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-04a4 dis:Alpha Airside VAV 1-2-62 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-04a5 dis:Alpha Airside VAV 1-2-62 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-04a4 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-04a6 dis:Alpha Airside VAV 1-2-62 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-04a4 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-04a7 dis:Alpha Airside VAV 1-2-62 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-04a4 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-04a8 dis:Alpha Airside VAV 1-2-62 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-04a4 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-04a9 dis:Alpha Airside VAV 1-2-62 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-04a4 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-04aa dis:Alpha Airside VAV 1-2-62 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-04a4 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-04ab dis:Alpha Airside VAV 1-2-62 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-04a4 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-04ac dis:Alpha Airside VAV 1-2-62 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-04a4 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-04ad dis:Alpha Airside VAV 1-2-62 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-04a4 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-04ae dis:Alpha Airside VAV 1-2-62 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-04a4 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-04af dis:Alpha Airside VAV 1-2-62 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-04a4 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-04b0 dis:Alpha Airside VAV 1-2-63 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-04b1 dis:Alpha Airside VAV 1-2-63 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-04b0 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-04b2 dis:Alpha Airside VAV 1-2-63 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-04b0 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-04b3 dis:Alpha Airside VAV 1-2-63 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-04b0 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-04b4 dis:Alpha Airside VAV 1-2-63 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-04b0 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-04b5 dis:Alpha Airside VAV 1-2-63 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-04b0 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-04b6 dis:Alpha Airside VAV 1-2-63 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-04b0 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-04b7 dis:Alpha Airside VAV 1-2-63 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-04b0 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-04b8 dis:Alpha Airside VAV 1-2-63 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-04b0 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-04b9 dis:Alpha Airside VAV 1-2-63 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-04b0 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-04ba dis:Alpha Airside VAV 1-2-63 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-04b0 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-04bb dis:Alpha Airside VAV 1-2-63 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-04b0 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-04bc dis:Alpha Airside VAV 1-2-64 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-04bd dis:Alpha Airside VAV 1-2-64 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-04bc his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-04be dis:Alpha Airside VAV 1-2-64 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-04bc flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-04bf dis:Alpha Airside VAV 1-2-64 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-04bc flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-04c0 dis:Alpha Airside VAV 1-2-64 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-04bc his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-04c1 dis:Alpha Airside VAV 1-2-64 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-04bc heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-04c2 dis:Alpha Airside VAV 1-2-64 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-04bc his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-04c3 dis:Alpha Airside VAV 1-2-64 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-04bc his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-04c4 dis:Alpha Airside VAV 1-2-64 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-04bc heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-04c5 dis:Alpha Airside VAV 1-2-64 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-04bc his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-04c6 dis:Alpha Airside VAV 1-2-64 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-04bc heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-04c7 dis:Alpha Airside VAV 1-2-64 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-04bc his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-04c8 dis:Alpha Airside VAV 1-2-65 airRef:@a-0001 equip equipRef:@a-0001 hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-04c9 dis:Alpha Airside VAV 1-2-65 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-04c8 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-04ca dis:Alpha Airside VAV 1-2-65 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-04c8 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-04cb dis:Alpha Airside VAV 1-2-65 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-04c8 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-04cc dis:Alpha Airside VAV 1-2-65 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-04c8 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-04cd dis:Alpha Airside VAV 1-2-65 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-04c8 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-04ce dis:Alpha Airside VAV 1-2-65 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-04c8 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-04cf dis:Alpha Airside VAV 1-2-65 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-04c8 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-04d0 dis:Alpha Airside VAV 1-2-65 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-04c8 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-04d1 dis:Alpha Airside VAV 1-2-65 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-04c8 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-04d2 dis:Alpha Airside VAV 1-2-66 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-04d3 dis:Alpha Airside VAV 1-2-66 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-04d2 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-04d4 dis:Alpha Airside VAV 1-2-66 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-04d2 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-04d5 dis:Alpha Airside VAV 1-2-66 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-04d2 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-04d6 dis:Alpha Airside VAV 1-2-66 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-04d2 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-04d7 dis:Alpha Airside VAV 1-2-66 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-04d2 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-04d8 dis:Alpha Airside VAV 1-2-66 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-04d2 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-04d9 dis:Alpha Airside VAV 1-2-66 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-04d2 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-04da dis:Alpha Airside VAV 1-2-66 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-04d2 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-04db dis:Alpha Airside VAV 1-2-66 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-04d2 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-04dc dis:Alpha Airside VAV 1-2-66 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-04d2 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-04dd dis:Alpha Airside VAV 1-2-66 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-04d2 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-04de dis:Alpha Airside VAV 1-2-67 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-04df dis:Alpha Airside VAV 1-2-67 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-04de his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-04e0 dis:Alpha Airside VAV 1-2-67 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-04de flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-04e1 dis:Alpha Airside VAV 1-2-67 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-04de flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-04e2 dis:Alpha Airside VAV 1-2-67 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-04de his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-04e3 dis:Alpha Airside VAV 1-2-67 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-04de heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-04e4 dis:Alpha Airside VAV 1-2-67 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-04de his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-04e5 dis:Alpha Airside VAV 1-2-67 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-04de his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-04e6 dis:Alpha Airside VAV 1-2-67 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-04de heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-04e7 dis:Alpha Airside VAV 1-2-67 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-04de his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-04e8 dis:Alpha Airside VAV 1-2-67 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-04de heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-04e9 dis:Alpha Airside VAV 1-2-67 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-04de his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-04ea dis:Alpha Airside VAV 1-2-68 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-04eb dis:Alpha Airside VAV 1-2-68 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-04ea his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-04ec dis:Alpha Airside VAV 1-2-68 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-04ea flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-04ed dis:Alpha Airside VAV 1-2-68 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-04ea flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-04ee dis:Alpha Airside VAV 1-2-68 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-04ea his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-04ef dis:Alpha Airside VAV 1-2-68 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-04ea heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-04f0 dis:Alpha Airside VAV 1-2-68 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-04ea his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-04f1 dis:Alpha Airside VAV 1-2-68 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-04ea his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-04f2 dis:Alpha Airside VAV 1-2-68 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-04ea heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-04f3 dis:Alpha Airside VAV 1-2-68 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-04ea his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-04f4 dis:Alpha Airside VAV 1-2-68 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-04ea heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-04f5 dis:Alpha Airside VAV 1-2-68 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-04ea his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-04f6 dis:Alpha Airside VAV 1-2-69 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-04f7 dis:Alpha Airside VAV 1-2-69 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-04f6 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-04f8 dis:Alpha Airside VAV 1-2-69 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-04f6 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-04f9 dis:Alpha Airside VAV 1-2-69 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-04f6 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-04fa dis:Alpha Airside VAV 1-2-69 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-04f6 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-04fb dis:Alpha Airside VAV 1-2-69 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-04f6 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-04fc dis:Alpha Airside VAV 1-2-69 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-04f6 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-04fd dis:Alpha Airside VAV 1-2-69 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-04f6 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-04fe dis:Alpha Airside VAV 1-2-69 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-04f6 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-04ff dis:Alpha Airside VAV 1-2-69 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-04f6 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0500 dis:Alpha Airside VAV 1-2-69 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-04f6 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0501 dis:Alpha Airside VAV 1-2-69 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-04f6 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0502 dis:Alpha Airside VAV 1-2-7 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0503 dis:Alpha Airside VAV 1-2-7 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0502 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0504 dis:Alpha Airside VAV 1-2-7 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0502 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0505 dis:Alpha Airside VAV 1-2-7 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0502 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0506 dis:Alpha Airside VAV 1-2-7 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0502 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0507 dis:Alpha Airside VAV 1-2-7 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0502 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0508 dis:Alpha Airside VAV 1-2-7 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0502 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0509 dis:Alpha Airside VAV 1-2-7 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0502 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-050a dis:Alpha Airside VAV 1-2-7 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0502 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-050b dis:Alpha Airside VAV 1-2-7 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0502 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-050c dis:Alpha Airside VAV 1-2-7 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0502 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-050d dis:Alpha Airside VAV 1-2-7 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0502 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-050e dis:Alpha Airside VAV 1-2-70 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-050f dis:Alpha Airside VAV 1-2-70 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-050e his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0510 dis:Alpha Airside VAV 1-2-70 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-050e flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0511 dis:Alpha Airside VAV 1-2-70 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-050e flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0512 dis:Alpha Airside VAV 1-2-70 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-050e his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0513 dis:Alpha Airside VAV 1-2-70 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-050e heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0514 dis:Alpha Airside VAV 1-2-70 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-050e his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0515 dis:Alpha Airside VAV 1-2-70 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-050e his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0516 dis:Alpha Airside VAV 1-2-70 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-050e heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0517 dis:Alpha Airside VAV 1-2-70 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-050e his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0518 dis:Alpha Airside VAV 1-2-70 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-050e heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0519 dis:Alpha Airside VAV 1-2-70 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-050e his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-051a dis:Alpha Airside VAV 1-2-71 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-051b dis:Alpha Airside VAV 1-2-71 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-051a his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-051c dis:Alpha Airside VAV 1-2-71 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-051a flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-051d dis:Alpha Airside VAV 1-2-71 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-051a flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-051e dis:Alpha Airside VAV 1-2-71 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-051a his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-051f dis:Alpha Airside VAV 1-2-71 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-051a heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0520 dis:Alpha Airside VAV 1-2-71 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-051a his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0521 dis:Alpha Airside VAV 1-2-71 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-051a his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0522 dis:Alpha Airside VAV 1-2-71 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-051a heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0523 dis:Alpha Airside VAV 1-2-71 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-051a his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0524 dis:Alpha Airside VAV 1-2-71 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-051a heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0525 dis:Alpha Airside VAV 1-2-71 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-051a his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0526 dis:Alpha Airside VAV 1-2-72 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0527 dis:Alpha Airside VAV 1-2-72 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0526 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0528 dis:Alpha Airside VAV 1-2-72 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0526 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0529 dis:Alpha Airside VAV 1-2-72 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0526 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-052a dis:Alpha Airside VAV 1-2-72 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0526 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-052b dis:Alpha Airside VAV 1-2-72 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0526 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-052c dis:Alpha Airside VAV 1-2-72 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0526 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-052d dis:Alpha Airside VAV 1-2-72 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0526 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-052e dis:Alpha Airside VAV 1-2-72 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0526 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-052f dis:Alpha Airside VAV 1-2-72 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0526 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0530 dis:Alpha Airside VAV 1-2-72 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0526 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0531 dis:Alpha Airside VAV 1-2-72 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0526 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0532 dis:Alpha Airside VAV 1-2-73 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0533 dis:Alpha Airside VAV 1-2-73 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0532 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0534 dis:Alpha Airside VAV 1-2-73 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0532 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0535 dis:Alpha Airside VAV 1-2-73 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0532 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0536 dis:Alpha Airside VAV 1-2-73 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0532 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0537 dis:Alpha Airside VAV 1-2-73 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0532 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0538 dis:Alpha Airside VAV 1-2-73 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0532 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0539 dis:Alpha Airside VAV 1-2-73 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0532 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-053a dis:Alpha Airside VAV 1-2-73 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0532 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-053b dis:Alpha Airside VAV 1-2-73 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0532 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-053c dis:Alpha Airside VAV 1-2-73 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0532 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-053d dis:Alpha Airside VAV 1-2-73 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0532 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-053e dis:Alpha Airside VAV 1-2-74 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-053f dis:Alpha Airside VAV 1-2-74 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-053e his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0540 dis:Alpha Airside VAV 1-2-74 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-053e flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0541 dis:Alpha Airside VAV 1-2-74 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-053e flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0542 dis:Alpha Airside VAV 1-2-74 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-053e his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0543 dis:Alpha Airside VAV 1-2-74 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-053e heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0544 dis:Alpha Airside VAV 1-2-74 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-053e his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0545 dis:Alpha Airside VAV 1-2-74 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-053e his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0546 dis:Alpha Airside VAV 1-2-74 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-053e heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0547 dis:Alpha Airside VAV 1-2-74 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-053e his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0548 dis:Alpha Airside VAV 1-2-74 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-053e heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0549 dis:Alpha Airside VAV 1-2-74 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-053e his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-054a dis:Alpha Airside VAV 1-2-75 airRef:@a-0001 equip equipRef:@a-0001 hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-054b dis:Alpha Airside VAV 1-2-75 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-054a his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-054c dis:Alpha Airside VAV 1-2-75 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-054a flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-054d dis:Alpha Airside VAV 1-2-75 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-054a flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-054e dis:Alpha Airside VAV 1-2-75 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-054a his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-054f dis:Alpha Airside VAV 1-2-75 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-054a his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0550 dis:Alpha Airside VAV 1-2-75 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-054a heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0551 dis:Alpha Airside VAV 1-2-75 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-054a his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0552 dis:Alpha Airside VAV 1-2-75 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-054a heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0553 dis:Alpha Airside VAV 1-2-75 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-054a his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0554 dis:Alpha Airside VAV 1-2-76 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0555 dis:Alpha Airside VAV 1-2-76 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0554 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0556 dis:Alpha Airside VAV 1-2-76 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0554 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0557 dis:Alpha Airside VAV 1-2-76 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0554 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0558 dis:Alpha Airside VAV 1-2-76 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0554 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0559 dis:Alpha Airside VAV 1-2-76 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0554 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-055a dis:Alpha Airside VAV 1-2-76 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0554 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-055b dis:Alpha Airside VAV 1-2-76 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0554 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-055c dis:Alpha Airside VAV 1-2-76 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0554 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-055d dis:Alpha Airside VAV 1-2-76 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0554 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-055e dis:Alpha Airside VAV 1-2-76 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0554 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-055f dis:Alpha Airside VAV 1-2-76 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0554 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0560 dis:Alpha Airside VAV 1-2-78 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0561 dis:Alpha Airside VAV 1-2-78 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0560 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0562 dis:Alpha Airside VAV 1-2-78 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0560 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0563 dis:Alpha Airside VAV 1-2-78 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0560 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0564 dis:Alpha Airside VAV 1-2-78 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0560 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0565 dis:Alpha Airside VAV 1-2-78 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0560 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0566 dis:Alpha Airside VAV 1-2-78 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0560 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0567 dis:Alpha Airside VAV 1-2-78 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0560 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0568 dis:Alpha Airside VAV 1-2-78 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0560 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0569 dis:Alpha Airside VAV 1-2-78 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0560 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-056a dis:Alpha Airside VAV 1-2-78 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0560 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-056b dis:Alpha Airside VAV 1-2-78 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0560 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-056c dis:Alpha Airside VAV 1-2-79 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-056d dis:Alpha Airside VAV 1-2-79 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-056c his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-056e dis:Alpha Airside VAV 1-2-79 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-056c flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-056f dis:Alpha Airside VAV 1-2-79 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-056c flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0570 dis:Alpha Airside VAV 1-2-79 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-056c his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0571 dis:Alpha Airside VAV 1-2-79 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-056c heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0572 dis:Alpha Airside VAV 1-2-79 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-056c his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0573 dis:Alpha Airside VAV 1-2-79 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-056c his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0574 dis:Alpha Airside VAV 1-2-79 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-056c heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0575 dis:Alpha Airside VAV 1-2-79 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-056c his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0576 dis:Alpha Airside VAV 1-2-79 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-056c heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0577 dis:Alpha Airside VAV 1-2-79 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-056c his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0578 dis:Alpha Airside VAV 1-2-8 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0579 dis:Alpha Airside VAV 1-2-8 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0578 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-057a dis:Alpha Airside VAV 1-2-8 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0578 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-057b dis:Alpha Airside VAV 1-2-8 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0578 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-057c dis:Alpha Airside VAV 1-2-8 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0578 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-057d dis:Alpha Airside VAV 1-2-8 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0578 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-057e dis:Alpha Airside VAV 1-2-8 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0578 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-057f dis:Alpha Airside VAV 1-2-8 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0578 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0580 dis:Alpha Airside VAV 1-2-8 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0578 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0581 dis:Alpha Airside VAV 1-2-8 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0578 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0582 dis:Alpha Airside VAV 1-2-8 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0578 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0583 dis:Alpha Airside VAV 1-2-8 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0578 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0584 dis:Alpha Airside VAV 1-2-80 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0585 dis:Alpha Airside VAV 1-2-80 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0584 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0586 dis:Alpha Airside VAV 1-2-80 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0584 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0587 dis:Alpha Airside VAV 1-2-80 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0584 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0588 dis:Alpha Airside VAV 1-2-80 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0584 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0589 dis:Alpha Airside VAV 1-2-80 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0584 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-058a dis:Alpha Airside VAV 1-2-80 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0584 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-058b dis:Alpha Airside VAV 1-2-80 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0584 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-058c dis:Alpha Airside VAV 1-2-80 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0584 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-058d dis:Alpha Airside VAV 1-2-80 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0584 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-058e dis:Alpha Airside VAV 1-2-80 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0584 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-058f dis:Alpha Airside VAV 1-2-80 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0584 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0590 dis:Alpha Airside VAV 1-2-81 airRef:@a-0001 equip equipRef:@a-0001 hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0591 dis:Alpha Airside VAV 1-2-81 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0590 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0592 dis:Alpha Airside VAV 1-2-81 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0590 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0593 dis:Alpha Airside VAV 1-2-81 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0590 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0594 dis:Alpha Airside VAV 1-2-81 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0590 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0595 dis:Alpha Airside VAV 1-2-81 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0590 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0596 dis:Alpha Airside VAV 1-2-81 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0590 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0597 dis:Alpha Airside VAV 1-2-81 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0590 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0598 dis:Alpha Airside VAV 1-2-81 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0590 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0599 dis:Alpha Airside VAV 1-2-81 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0590 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-059a dis:Alpha Airside VAV 1-2-82 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-059b dis:Alpha Airside VAV 1-2-82 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-059a his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-059c dis:Alpha Airside VAV 1-2-82 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-059a flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-059d dis:Alpha Airside VAV 1-2-82 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-059a flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-059e dis:Alpha Airside VAV 1-2-82 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-059a his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-059f dis:Alpha Airside VAV 1-2-82 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-059a heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-05a0 dis:Alpha Airside VAV 1-2-82 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-059a his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-05a1 dis:Alpha Airside VAV 1-2-82 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-059a his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-05a2 dis:Alpha Airside VAV 1-2-82 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-059a heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-05a3 dis:Alpha Airside VAV 1-2-82 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-059a his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-05a4 dis:Alpha Airside VAV 1-2-82 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-059a heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-05a5 dis:Alpha Airside VAV 1-2-82 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-059a his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-05a6 dis:Alpha Airside VAV 1-2-83 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-05a7 dis:Alpha Airside VAV 1-2-83 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-05a6 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-05a8 dis:Alpha Airside VAV 1-2-83 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-05a6 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-05a9 dis:Alpha Airside VAV 1-2-83 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-05a6 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-05aa dis:Alpha Airside VAV 1-2-83 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-05a6 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-05ab dis:Alpha Airside VAV 1-2-83 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-05a6 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-05ac dis:Alpha Airside VAV 1-2-83 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-05a6 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-05ad dis:Alpha Airside VAV 1-2-83 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-05a6 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-05ae dis:Alpha Airside VAV 1-2-83 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-05a6 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-05af dis:Alpha Airside VAV 1-2-83 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-05a6 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-05b0 dis:Alpha Airside VAV 1-2-83 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-05a6 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-05b1 dis:Alpha Airside VAV 1-2-83 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-05a6 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-05b2 dis:Alpha Airside VAV 1-2-84 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-05b3 dis:Alpha Airside VAV 1-2-84 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-05b2 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-05b4 dis:Alpha Airside VAV 1-2-84 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-05b2 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-05b5 dis:Alpha Airside VAV 1-2-84 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-05b2 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-05b6 dis:Alpha Airside VAV 1-2-84 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-05b2 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-05b7 dis:Alpha Airside VAV 1-2-84 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-05b2 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-05b8 dis:Alpha Airside VAV 1-2-84 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-05b2 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-05b9 dis:Alpha Airside VAV 1-2-84 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-05b2 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-05ba dis:Alpha Airside VAV 1-2-84 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-05b2 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-05bb dis:Alpha Airside VAV 1-2-84 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-05b2 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-05bc dis:Alpha Airside VAV 1-2-84 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-05b2 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-05bd dis:Alpha Airside VAV 1-2-84 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-05b2 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-05be dis:Alpha Airside VAV 1-2-85 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-05bf dis:Alpha Airside VAV 1-2-85 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-05be his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-05c0 dis:Alpha Airside VAV 1-2-85 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-05be flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-05c1 dis:Alpha Airside VAV 1-2-85 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-05be flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-05c2 dis:Alpha Airside VAV 1-2-85 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-05be his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-05c3 dis:Alpha Airside VAV 1-2-85 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-05be heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-05c4 dis:Alpha Airside VAV 1-2-85 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-05be his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-05c5 dis:Alpha Airside VAV 1-2-85 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-05be his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-05c6 dis:Alpha Airside VAV 1-2-85 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-05be heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-05c7 dis:Alpha Airside VAV 1-2-85 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-05be his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-05c8 dis:Alpha Airside VAV 1-2-85 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-05be heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-05c9 dis:Alpha Airside VAV 1-2-85 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-05be his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-05ca dis:Alpha Airside VAV 1-2-86 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-05cb dis:Alpha Airside VAV 1-2-86 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-05ca his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-05cc dis:Alpha Airside VAV 1-2-86 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-05ca flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-05cd dis:Alpha Airside VAV 1-2-86 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-05ca flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-05ce dis:Alpha Airside VAV 1-2-86 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-05ca his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-05cf dis:Alpha Airside VAV 1-2-86 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-05ca heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-05d0 dis:Alpha Airside VAV 1-2-86 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-05ca his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-05d1 dis:Alpha Airside VAV 1-2-86 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-05ca his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-05d2 dis:Alpha Airside VAV 1-2-86 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-05ca heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-05d3 dis:Alpha Airside VAV 1-2-86 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-05ca his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-05d4 dis:Alpha Airside VAV 1-2-86 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-05ca heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-05d5 dis:Alpha Airside VAV 1-2-86 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-05ca his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-05d6 dis:Alpha Airside VAV 1-2-87 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-05d7 dis:Alpha Airside VAV 1-2-87 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-05d6 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-05d8 dis:Alpha Airside VAV 1-2-87 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-05d6 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-05d9 dis:Alpha Airside VAV 1-2-87 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-05d6 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-05da dis:Alpha Airside VAV 1-2-87 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-05d6 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-05db dis:Alpha Airside VAV 1-2-87 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-05d6 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-05dc dis:Alpha Airside VAV 1-2-87 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-05d6 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-05dd dis:Alpha Airside VAV 1-2-87 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-05d6 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-05de dis:Alpha Airside VAV 1-2-87 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-05d6 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-05df dis:Alpha Airside VAV 1-2-87 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-05d6 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-05e0 dis:Alpha Airside VAV 1-2-87 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-05d6 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-05e1 dis:Alpha Airside VAV 1-2-87 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-05d6 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-05e2 dis:Alpha Airside VAV 1-2-88 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-05e3 dis:Alpha Airside VAV 1-2-88 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-05e2 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-05e4 dis:Alpha Airside VAV 1-2-88 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-05e2 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-05e5 dis:Alpha Airside VAV 1-2-88 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-05e2 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-05e6 dis:Alpha Airside VAV 1-2-88 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-05e2 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-05e7 dis:Alpha Airside VAV 1-2-88 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-05e2 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-05e8 dis:Alpha Airside VAV 1-2-88 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-05e2 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-05e9 dis:Alpha Airside VAV 1-2-88 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-05e2 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-05ea dis:Alpha Airside VAV 1-2-88 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-05e2 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-05eb dis:Alpha Airside VAV 1-2-88 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-05e2 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-05ec dis:Alpha Airside VAV 1-2-88 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-05e2 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-05ed dis:Alpha Airside VAV 1-2-88 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-05e2 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-05ee dis:Alpha Airside VAV 1-2-89 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-05ef dis:Alpha Airside VAV 1-2-89 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-05ee his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-05f0 dis:Alpha Airside VAV 1-2-89 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-05ee flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-05f1 dis:Alpha Airside VAV 1-2-89 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-05ee flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-05f2 dis:Alpha Airside VAV 1-2-89 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-05ee his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-05f3 dis:Alpha Airside VAV 1-2-89 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-05ee heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-05f4 dis:"Alpha Airside VAV 1-2-89 Relief Air Fan S/S Command" air cmd cur custom:{description:"Decon EF S/S" relief} equipRef:@a-05ee exhaust fan his hisMode:cov kind:Bool point run siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-05f5 dis:Alpha Airside VAV 1-2-89 Relief Fan Status air cur custom:{description:"Decon EF Status" relief} equipRef:@a-05ee exhaust fan his hisMode:cov kind:Bool point run sensor siteRef:@a-0000 tz:Denver --- id:@a-05f6 dis:Alpha Airside VAV 1-2-89 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-05ee his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-05f7 dis:Alpha Airside VAV 1-2-89 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-05ee his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-05f8 dis:Alpha Airside VAV 1-2-89 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-05ee heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-05f9 dis:Alpha Airside VAV 1-2-89 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-05ee his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-05fa dis:Alpha Airside VAV 1-2-89 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-05ee heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-05fb dis:Alpha Airside VAV 1-2-89 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-05ee his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-05fc dis:Alpha Airside VAV 1-2-9 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-05fd dis:Alpha Airside VAV 1-2-9 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-05fc his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-05fe dis:Alpha Airside VAV 1-2-9 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-05fc flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-05ff dis:Alpha Airside VAV 1-2-9 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-05fc flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0600 dis:Alpha Airside VAV 1-2-9 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-05fc his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0601 dis:Alpha Airside VAV 1-2-9 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-05fc heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0602 dis:Alpha Airside VAV 1-2-9 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-05fc his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0603 dis:Alpha Airside VAV 1-2-9 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-05fc his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0604 dis:Alpha Airside VAV 1-2-9 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-05fc heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0605 dis:Alpha Airside VAV 1-2-9 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-05fc his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0606 dis:Alpha Airside VAV 1-2-9 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-05fc heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0607 dis:Alpha Airside VAV 1-2-9 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-05fc his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0608 dis:Alpha Airside VAV 1-2-90 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0609 dis:Alpha Airside VAV 1-2-90 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0608 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-060a dis:Alpha Airside VAV 1-2-90 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0608 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-060b dis:Alpha Airside VAV 1-2-90 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0608 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-060c dis:Alpha Airside VAV 1-2-90 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0608 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-060d dis:Alpha Airside VAV 1-2-90 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0608 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-060e dis:Alpha Airside VAV 1-2-90 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0608 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-060f dis:Alpha Airside VAV 1-2-90 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0608 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0610 dis:Alpha Airside VAV 1-2-90 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0608 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0611 dis:Alpha Airside VAV 1-2-90 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0608 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0612 dis:Alpha Airside VAV 1-2-90 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0608 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0613 dis:Alpha Airside VAV 1-2-90 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0608 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0614 dis:Alpha Airside VAV 1-2-91 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0615 dis:Alpha Airside VAV 1-2-91 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0614 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0616 dis:Alpha Airside VAV 1-2-91 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0614 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0617 dis:Alpha Airside VAV 1-2-91 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0614 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0618 dis:Alpha Airside VAV 1-2-91 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0614 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0619 dis:Alpha Airside VAV 1-2-91 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0614 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-061a dis:Alpha Airside VAV 1-2-91 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0614 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-061b dis:Alpha Airside VAV 1-2-91 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0614 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-061c dis:Alpha Airside VAV 1-2-91 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0614 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-061d dis:Alpha Airside VAV 1-2-91 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0614 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-061e dis:Alpha Airside VAV 1-2-91 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0614 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-061f dis:Alpha Airside VAV 1-2-91 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0614 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0620 dis:Alpha Airside VAV 1-2-92 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0621 dis:Alpha Airside VAV 1-2-92 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0620 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0622 dis:Alpha Airside VAV 1-2-92 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0620 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0623 dis:Alpha Airside VAV 1-2-92 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0620 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0624 dis:Alpha Airside VAV 1-2-92 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0620 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0625 dis:Alpha Airside VAV 1-2-92 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0620 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0626 dis:Alpha Airside VAV 1-2-92 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0620 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0627 dis:Alpha Airside VAV 1-2-92 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0620 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0628 dis:Alpha Airside VAV 1-2-92 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0620 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0629 dis:Alpha Airside VAV 1-2-92 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0620 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-062a dis:Alpha Airside VAV 1-2-92 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0620 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-062b dis:Alpha Airside VAV 1-2-92 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0620 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-062c dis:Alpha Airside VAV 1-2-93 airRef:@a-0001 equip equipRef:@a-0001 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-062d dis:Alpha Airside VAV 1-2-93 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-062c his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-062e dis:Alpha Airside VAV 1-2-93 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-062c flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-062f dis:Alpha Airside VAV 1-2-93 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-062c flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0630 dis:Alpha Airside VAV 1-2-93 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-062c his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0631 dis:Alpha Airside VAV 1-2-93 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-062c heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0632 dis:Alpha Airside VAV 1-2-93 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-062c his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0633 dis:Alpha Airside VAV 1-2-93 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-062c his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0634 dis:Alpha Airside VAV 1-2-93 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-062c heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0635 dis:Alpha Airside VAV 1-2-93 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-062c his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0636 dis:Alpha Airside VAV 1-2-93 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-062c heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0637 dis:Alpha Airside VAV 1-2-93 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-062c his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0638 dis:Alpha Airside VAV 1-2-94 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0639 dis:Alpha Airside VAV 1-2-94 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0638 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-063a dis:Alpha Airside VAV 1-2-94 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0638 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-063b dis:Alpha Airside VAV 1-2-94 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0638 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-063c dis:Alpha Airside VAV 1-2-94 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0638 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-063d dis:Alpha Airside VAV 1-2-94 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0638 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-063e dis:Alpha Airside VAV 1-2-94 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0638 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-063f dis:Alpha Airside VAV 1-2-94 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0638 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0640 dis:Alpha Airside VAV 1-2-94 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0638 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0641 dis:Alpha Airside VAV 1-2-94 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0638 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0642 dis:Alpha Airside VAV 1-2-94 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0638 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0643 dis:Alpha Airside VAV 1-2-94 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0638 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0644 dis:Alpha Airside VAV 1-2-95 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0645 dis:Alpha Airside VAV 1-2-95 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0644 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0646 dis:Alpha Airside VAV 1-2-95 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0644 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0647 dis:Alpha Airside VAV 1-2-95 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0644 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0648 dis:Alpha Airside VAV 1-2-95 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0644 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0649 dis:Alpha Airside VAV 1-2-95 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0644 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-064a dis:Alpha Airside VAV 1-2-95 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0644 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-064b dis:Alpha Airside VAV 1-2-95 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0644 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-064c dis:Alpha Airside VAV 1-2-95 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0644 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-064d dis:Alpha Airside VAV 1-2-95 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0644 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-064e dis:Alpha Airside VAV 1-2-95 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0644 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-064f dis:Alpha Airside VAV 1-2-95 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0644 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0650 dis:Alpha Airside VAV 1-2-96 airRef:@a-0001 equip equipRef:@a-0001 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0651 dis:Alpha Airside VAV 1-2-96 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0650 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0652 dis:Alpha Airside VAV 1-2-96 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0650 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0653 dis:Alpha Airside VAV 1-2-96 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0650 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0654 dis:Alpha Airside VAV 1-2-96 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0650 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0655 dis:Alpha Airside VAV 1-2-96 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0650 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0656 dis:Alpha Airside VAV 1-2-96 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0650 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0657 dis:Alpha Airside VAV 1-2-96 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0650 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0658 dis:Alpha Airside VAV 1-2-96 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0650 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0659 dis:Alpha Airside VAV 1-2-96 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0650 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-065a dis:Alpha Airside VAV 1-2-96 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0650 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-065b dis:Alpha Airside VAV 1-2-96 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0650 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-065c dis:Alpha Airside VAV 1-3-1 airRef:@a-0020 equip equipRef:@a-0020 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-065d dis:Alpha Airside VAV 1-3-1 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-065c his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-065e dis:Alpha Airside VAV 1-3-1 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-065c flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-065f dis:Alpha Airside VAV 1-3-1 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-065c flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0660 dis:Alpha Airside VAV 1-3-1 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-065c his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0661 dis:Alpha Airside VAV 1-3-1 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-065c heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0662 dis:Alpha Airside VAV 1-3-1 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-065c his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0663 dis:Alpha Airside VAV 1-3-1 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-065c his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0664 dis:Alpha Airside VAV 1-3-1 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-065c heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0665 dis:Alpha Airside VAV 1-3-1 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-065c his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0666 dis:Alpha Airside VAV 1-3-1 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-065c heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0667 dis:Alpha Airside VAV 1-3-1 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-065c his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0668 dis:Alpha Airside VAV 1-3-10 airRef:@a-0020 equip equipRef:@a-0020 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0669 dis:Alpha Airside VAV 1-3-10 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0668 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-066a dis:Alpha Airside VAV 1-3-10 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0668 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-066b dis:Alpha Airside VAV 1-3-10 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0668 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-066c dis:Alpha Airside VAV 1-3-10 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0668 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-066d dis:Alpha Airside VAV 1-3-10 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0668 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-066e dis:Alpha Airside VAV 1-3-10 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0668 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-066f dis:Alpha Airside VAV 1-3-10 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0668 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0670 dis:Alpha Airside VAV 1-3-10 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0668 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0671 dis:Alpha Airside VAV 1-3-10 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0668 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0672 dis:Alpha Airside VAV 1-3-10 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0668 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0673 dis:Alpha Airside VAV 1-3-10 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0668 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0674 dis:Alpha Airside VAV 1-3-11 airRef:@a-0020 equip equipRef:@a-0020 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0675 dis:Alpha Airside VAV 1-3-11 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0674 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0676 dis:Alpha Airside VAV 1-3-11 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0674 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0677 dis:Alpha Airside VAV 1-3-11 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0674 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0678 dis:Alpha Airside VAV 1-3-11 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0674 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0679 dis:Alpha Airside VAV 1-3-11 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0674 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-067a dis:Alpha Airside VAV 1-3-11 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0674 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-067b dis:Alpha Airside VAV 1-3-11 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0674 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-067c dis:Alpha Airside VAV 1-3-11 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0674 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-067d dis:Alpha Airside VAV 1-3-11 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0674 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-067e dis:Alpha Airside VAV 1-3-11 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0674 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-067f dis:Alpha Airside VAV 1-3-11 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0674 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0680 dis:Alpha Airside VAV 1-3-12 airRef:@a-0020 equip equipRef:@a-0020 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0681 dis:Alpha Airside VAV 1-3-12 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0680 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0682 dis:Alpha Airside VAV 1-3-12 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0680 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0683 dis:Alpha Airside VAV 1-3-12 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0680 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0684 dis:Alpha Airside VAV 1-3-12 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0680 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0685 dis:Alpha Airside VAV 1-3-12 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0680 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0686 dis:Alpha Airside VAV 1-3-12 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0680 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0687 dis:Alpha Airside VAV 1-3-12 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0680 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0688 dis:Alpha Airside VAV 1-3-12 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0680 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0689 dis:Alpha Airside VAV 1-3-12 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0680 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-068a dis:Alpha Airside VAV 1-3-12 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0680 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-068b dis:Alpha Airside VAV 1-3-12 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0680 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-068c dis:Alpha Airside VAV 1-3-13 airRef:@a-0020 equip equipRef:@a-0020 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-068d dis:Alpha Airside VAV 1-3-13 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-068c his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-068e dis:Alpha Airside VAV 1-3-13 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-068c flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-068f dis:Alpha Airside VAV 1-3-13 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-068c flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0690 dis:Alpha Airside VAV 1-3-13 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-068c his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0691 dis:Alpha Airside VAV 1-3-13 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-068c heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0692 dis:Alpha Airside VAV 1-3-13 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-068c his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0693 dis:Alpha Airside VAV 1-3-13 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-068c his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0694 dis:Alpha Airside VAV 1-3-13 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-068c heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0695 dis:Alpha Airside VAV 1-3-13 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-068c his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0696 dis:Alpha Airside VAV 1-3-13 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-068c heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0697 dis:Alpha Airside VAV 1-3-13 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-068c his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0698 dis:Alpha Airside VAV 1-3-14 airRef:@a-0020 equip equipRef:@a-0020 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0699 dis:Alpha Airside VAV 1-3-14 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0698 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-069a dis:Alpha Airside VAV 1-3-14 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0698 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-069b dis:Alpha Airside VAV 1-3-14 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0698 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-069c dis:Alpha Airside VAV 1-3-14 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0698 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-069d dis:Alpha Airside VAV 1-3-14 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0698 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-069e dis:Alpha Airside VAV 1-3-14 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0698 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-069f dis:Alpha Airside VAV 1-3-14 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0698 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-06a0 dis:Alpha Airside VAV 1-3-14 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0698 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-06a1 dis:Alpha Airside VAV 1-3-14 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0698 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-06a2 dis:Alpha Airside VAV 1-3-14 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0698 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-06a3 dis:Alpha Airside VAV 1-3-14 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0698 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-06a4 dis:Alpha Airside VAV 1-3-15 airRef:@a-0020 equip equipRef:@a-0020 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-06a5 dis:Alpha Airside VAV 1-3-15 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-06a4 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-06a6 dis:Alpha Airside VAV 1-3-15 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-06a4 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-06a7 dis:Alpha Airside VAV 1-3-15 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-06a4 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-06a8 dis:Alpha Airside VAV 1-3-15 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-06a4 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-06a9 dis:Alpha Airside VAV 1-3-15 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-06a4 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-06aa dis:Alpha Airside VAV 1-3-15 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-06a4 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-06ab dis:Alpha Airside VAV 1-3-15 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-06a4 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-06ac dis:Alpha Airside VAV 1-3-15 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-06a4 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-06ad dis:Alpha Airside VAV 1-3-15 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-06a4 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-06ae dis:Alpha Airside VAV 1-3-15 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-06a4 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-06af dis:Alpha Airside VAV 1-3-15 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-06a4 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-06b0 dis:Alpha Airside VAV 1-3-16 airRef:@a-0020 equip equipRef:@a-0020 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-06b1 dis:Alpha Airside VAV 1-3-16 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-06b0 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-06b2 dis:Alpha Airside VAV 1-3-16 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-06b0 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-06b3 dis:Alpha Airside VAV 1-3-16 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-06b0 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-06b4 dis:Alpha Airside VAV 1-3-16 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-06b0 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-06b5 dis:Alpha Airside VAV 1-3-16 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-06b0 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-06b6 dis:Alpha Airside VAV 1-3-16 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-06b0 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-06b7 dis:Alpha Airside VAV 1-3-16 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-06b0 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-06b8 dis:Alpha Airside VAV 1-3-16 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-06b0 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-06b9 dis:Alpha Airside VAV 1-3-16 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-06b0 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-06ba dis:Alpha Airside VAV 1-3-16 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-06b0 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-06bb dis:Alpha Airside VAV 1-3-16 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-06b0 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-06bc dis:Alpha Airside VAV 1-3-17 airRef:@a-0020 equip equipRef:@a-0020 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-06bd dis:Alpha Airside VAV 1-3-17 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-06bc his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-06be dis:Alpha Airside VAV 1-3-17 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-06bc flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-06bf dis:Alpha Airside VAV 1-3-17 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-06bc flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-06c0 dis:Alpha Airside VAV 1-3-17 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-06bc his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-06c1 dis:Alpha Airside VAV 1-3-17 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-06bc heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-06c2 dis:Alpha Airside VAV 1-3-17 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-06bc his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-06c3 dis:Alpha Airside VAV 1-3-17 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-06bc his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-06c4 dis:Alpha Airside VAV 1-3-17 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-06bc heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-06c5 dis:Alpha Airside VAV 1-3-17 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-06bc his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-06c6 dis:Alpha Airside VAV 1-3-17 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-06bc heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-06c7 dis:Alpha Airside VAV 1-3-17 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-06bc his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-06c8 dis:Alpha Airside VAV 1-3-2 airRef:@a-0020 equip equipRef:@a-0020 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-06c9 dis:Alpha Airside VAV 1-3-2 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-06c8 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-06ca dis:Alpha Airside VAV 1-3-2 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-06c8 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-06cb dis:Alpha Airside VAV 1-3-2 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-06c8 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-06cc dis:Alpha Airside VAV 1-3-2 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-06c8 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-06cd dis:Alpha Airside VAV 1-3-2 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-06c8 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-06ce dis:Alpha Airside VAV 1-3-2 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-06c8 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-06cf dis:Alpha Airside VAV 1-3-2 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-06c8 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-06d0 dis:Alpha Airside VAV 1-3-2 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-06c8 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-06d1 dis:Alpha Airside VAV 1-3-2 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-06c8 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-06d2 dis:Alpha Airside VAV 1-3-2 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-06c8 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-06d3 dis:Alpha Airside VAV 1-3-2 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-06c8 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-06d4 dis:Alpha Airside VAV 1-3-3 airRef:@a-0020 equip equipRef:@a-0020 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-06d5 dis:Alpha Airside VAV 1-3-3 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-06d4 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-06d6 dis:Alpha Airside VAV 1-3-3 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-06d4 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-06d7 dis:Alpha Airside VAV 1-3-3 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-06d4 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-06d8 dis:Alpha Airside VAV 1-3-3 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-06d4 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-06d9 dis:Alpha Airside VAV 1-3-3 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-06d4 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-06da dis:Alpha Airside VAV 1-3-3 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-06d4 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-06db dis:Alpha Airside VAV 1-3-3 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-06d4 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-06dc dis:Alpha Airside VAV 1-3-3 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-06d4 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-06dd dis:Alpha Airside VAV 1-3-3 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-06d4 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-06de dis:Alpha Airside VAV 1-3-3 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-06d4 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-06df dis:Alpha Airside VAV 1-3-3 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-06d4 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-06e0 dis:Alpha Airside VAV 1-3-4 airRef:@a-0020 equip equipRef:@a-0020 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-06e1 dis:Alpha Airside VAV 1-3-4 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-06e0 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-06e2 dis:Alpha Airside VAV 1-3-4 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-06e0 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-06e3 dis:Alpha Airside VAV 1-3-4 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-06e0 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-06e4 dis:Alpha Airside VAV 1-3-4 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-06e0 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-06e5 dis:Alpha Airside VAV 1-3-4 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-06e0 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-06e6 dis:Alpha Airside VAV 1-3-4 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-06e0 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-06e7 dis:Alpha Airside VAV 1-3-4 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-06e0 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-06e8 dis:Alpha Airside VAV 1-3-4 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-06e0 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-06e9 dis:Alpha Airside VAV 1-3-4 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-06e0 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-06ea dis:Alpha Airside VAV 1-3-4 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-06e0 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-06eb dis:Alpha Airside VAV 1-3-4 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-06e0 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-06ec dis:Alpha Airside VAV 1-3-5 airRef:@a-0020 equip equipRef:@a-0020 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-06ed dis:Alpha Airside VAV 1-3-5 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-06ec his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-06ee dis:Alpha Airside VAV 1-3-5 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-06ec flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-06ef dis:Alpha Airside VAV 1-3-5 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-06ec flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-06f0 dis:Alpha Airside VAV 1-3-5 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-06ec his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-06f1 dis:Alpha Airside VAV 1-3-5 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-06ec heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-06f2 dis:Alpha Airside VAV 1-3-5 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-06ec his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-06f3 dis:Alpha Airside VAV 1-3-5 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-06ec his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-06f4 dis:Alpha Airside VAV 1-3-5 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-06ec heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-06f5 dis:Alpha Airside VAV 1-3-5 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-06ec his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-06f6 dis:Alpha Airside VAV 1-3-5 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-06ec heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-06f7 dis:Alpha Airside VAV 1-3-5 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-06ec his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-06f8 dis:Alpha Airside VAV 1-3-6 airRef:@a-0020 equip equipRef:@a-0020 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-06f9 dis:Alpha Airside VAV 1-3-6 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-06f8 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-06fa dis:Alpha Airside VAV 1-3-6 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-06f8 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-06fb dis:Alpha Airside VAV 1-3-6 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-06f8 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-06fc dis:Alpha Airside VAV 1-3-6 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-06f8 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-06fd dis:Alpha Airside VAV 1-3-6 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-06f8 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-06fe dis:Alpha Airside VAV 1-3-6 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-06f8 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-06ff dis:Alpha Airside VAV 1-3-6 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-06f8 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0700 dis:Alpha Airside VAV 1-3-6 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-06f8 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0701 dis:Alpha Airside VAV 1-3-6 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-06f8 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0702 dis:Alpha Airside VAV 1-3-6 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-06f8 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0703 dis:Alpha Airside VAV 1-3-6 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-06f8 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0704 dis:Alpha Airside VAV 1-3-7 airRef:@a-0020 equip equipRef:@a-0020 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0705 dis:Alpha Airside VAV 1-3-7 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0704 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0706 dis:Alpha Airside VAV 1-3-7 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0704 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0707 dis:Alpha Airside VAV 1-3-7 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0704 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0708 dis:Alpha Airside VAV 1-3-7 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0704 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0709 dis:Alpha Airside VAV 1-3-7 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0704 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-070a dis:Alpha Airside VAV 1-3-7 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0704 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-070b dis:Alpha Airside VAV 1-3-7 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0704 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-070c dis:Alpha Airside VAV 1-3-7 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0704 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-070d dis:Alpha Airside VAV 1-3-7 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0704 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-070e dis:Alpha Airside VAV 1-3-7 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0704 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-070f dis:Alpha Airside VAV 1-3-7 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0704 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0710 dis:Alpha Airside VAV 1-3-8 airRef:@a-0020 equip equipRef:@a-0020 fanPowered hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-0711 dis:Alpha Airside VAV 1-3-8 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-0710 his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0712 dis:Alpha Airside VAV 1-3-8 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-0710 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-0713 dis:Alpha Airside VAV 1-3-8 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-0710 flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0714 dis:Alpha Airside VAV 1-3-8 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-0710 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0715 dis:Alpha Airside VAV 1-3-8 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-0710 heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0716 dis:Alpha Airside VAV 1-3-8 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-0710 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0717 dis:Alpha Airside VAV 1-3-8 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-0710 his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0718 dis:Alpha Airside VAV 1-3-8 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-0710 heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0719 dis:Alpha Airside VAV 1-3-8 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-0710 his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-071a dis:Alpha Airside VAV 1-3-8 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-0710 heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-071b dis:Alpha Airside VAV 1-3-8 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-0710 his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-071c dis:Alpha Airside VAV 1-3-9 airRef:@a-0020 equip equipRef:@a-0020 hotWaterHeating hotWaterRef:@a-07da hvac singleDuct siteRef:@a-0000 thermostat vav --- id:@a-071d dis:Alpha Airside VAV 1-3-9 Air Damper air cmd cur custom:{description:"Damper Command"} damper discharge equipRef:@a-071c his kind:Number point siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-071e dis:Alpha Airside VAV 1-3-9 Discharge Air Flow air cur custom:{description:"Current Airflow"} discharge equipRef:@a-071c flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:cfm --- id:@a-071f dis:Alpha Airside VAV 1-3-9 Discharge Air Flow Setpoint air cur custom:{description:"Desired Airflow"} discharge effective equipRef:@a-071c flow his kind:Number point siteRef:@a-0000 sp tz:Denver unit:cfm --- id:@a-0720 dis:Alpha Airside VAV 1-3-9 Discharge Air Temp air cur custom:{description:"Discharge Air Temp"} discharge equipRef:@a-071c his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0721 dis:Alpha Airside VAV 1-3-9 Hot Water Valve cmd cur custom:{description:"Heating Valve Signal"} equipRef:@a-071c heat his hot kind:Number point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0722 dis:Alpha Airside VAV 1-3-9 Zone Air Temp air cur custom:{description:"Space Temperature"} equipRef:@a-071c his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F zone --- id:@a-0723 dis:Alpha Airside VAV 1-3-9 Zone Air Temp Occ Cooling Setpoint air cooling cur custom:{description:"Occupied Clg Setpoint"} equipRef:@a-071c his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0724 dis:Alpha Airside VAV 1-3-9 Zone Air Temp Occ Heating Setpoint air cur custom:{description:"Occupied Htg Setpoint"} equipRef:@a-071c heating his hisMode:cov kind:Number occ point siteRef:@a-0000 sp temp tz:Denver unit:°F zone --- id:@a-0725 dis:Alpha Airside VAV 1-3-9 Zone Air Temp Unocc Cooling Setpoint air cooling cur custom:{description:"Unoccupied Clg Sp"} equipRef:@a-071c his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0726 dis:Alpha Airside VAV 1-3-9 Zone Air Temp Unocc Heating Setpoint air cur custom:{description:"Unoccupied Htg Sp"} equipRef:@a-071c heating his hisMode:cov kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F unocc zone --- id:@a-0727 dis:Alpha Airside VAV 1-3-9 Zone Occupancy Mode cmd cur custom:{description:"Occupied status"} equipRef:@a-071c his hisMode:cov kind:Bool occupied point siteRef:@a-0000 tz:Denver zone --- id:@a-0728 dis:Alpha Utility Bills Elec Meter 1 elec equip meter siteRef:@a-0000 --- id:@a-0729 dis:Alpha Utility Bills Elec Meter 1 Cost custom:{cost} equipRef:@a-0728 his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"\$" --- id:@a-072a dis:Alpha Utility Bills Elec Meter 1 Energy elec energy equipRef:@a-0728 his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:kWh --- id:@a-072b dis:Alpha Utility Bills Elec Meter 1 Power Peak custom:{max} elec equipRef:@a-0728 his kind:Number point power sensor siteRef:@a-0000 tz:Denver unit:kW --- id:@a-072c dis:Alpha Utility Bills Elec Meter 2 elec equip meter siteRef:@a-0000 --- id:@a-072d dis:Alpha Utility Bills Elec Meter 2 Cost custom:{cost} equipRef:@a-072c his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"\$" --- id:@a-072e dis:Alpha Utility Bills Elec Meter 2 Energy elec energy equipRef:@a-072c his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:kWh --- id:@a-072f dis:Alpha Utility Bills Elec Meter 2 Power Peak custom:{max} elec equipRef:@a-072c his kind:Number point power sensor siteRef:@a-0000 tz:Denver unit:kW --- id:@a-0730 dis:Alpha Utility Bills Gas Meter 1 equip gas meter siteRef:@a-0000 --- id:@a-0731 dis:Alpha Utility Bills Gas Meter 1 Cost custom:{cost} equipRef:@a-0730 his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"\$" --- id:@a-0732 dis:Alpha Utility Bills Gas Meter 1 Energy energy equipRef:@a-0730 gas his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:therm --- id:@a-0733 dis:Alpha Utility Bills Gas Meter 2 equip gas meter siteRef:@a-0000 --- id:@a-0734 dis:Alpha Utility Bills Gas Meter 2 Cost custom:{cost} equipRef:@a-0733 his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"\$" --- id:@a-0735 dis:Alpha Utility Bills Gas Meter 2 Energy energy equipRef:@a-0733 gas his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:therm --- id:@a-0736 dis:Alpha Utility Bills Gas Meter 2 Transport Cost custom:{cost} equipRef:@a-0733 his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"\$" --- id:@a-0737 dis:Alpha Utility Bills Gas Meter 3 equip gas meter siteRef:@a-0000 --- id:@a-0738 dis:Alpha Utility Bills Gas Meter 3 Cost custom:{cost} equipRef:@a-0737 his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"\$" --- id:@a-0739 dis:Alpha Utility Bills Gas Meter 3 Energy energy equipRef:@a-0737 gas his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:therm --- id:@a-073a dis:Alpha Utility Bills Water Meter 1 equip siteRef:@a-0000 water --- id:@a-073b dis:Alpha Utility Bills Water Meter 1 Cost custom:{cost} equipRef:@a-073a his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"\$" --- id:@a-073c dis:Alpha Utility Bills Water Meter 1 Volume domestic equipRef:@a-073a his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:gal volume water --- id:@a-073d dis:Alpha Utility Bills Water Meter 2 equip siteRef:@a-0000 water --- id:@a-073e dis:Alpha Utility Bills Water Meter 2 Cost custom:{cost} equipRef:@a-073d his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"\$" --- id:@a-073f dis:Alpha Utility Bills Water Meter 2 Volume domestic equipRef:@a-073d his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:gal volume water --- id:@a-0740 dis:Alpha Utility Bills Water Meter 3 equip siteRef:@a-0000 water --- id:@a-0741 dis:Alpha Utility Bills Water Meter 3 Cost custom:{cost} equipRef:@a-0740 his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"\$" --- id:@a-0742 dis:Alpha Utility Bills Water Meter 3 Volume domestic equipRef:@a-0740 his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:gal volume water --- id:@a-0743 dis:Alpha Utility Bills Water Meter 4 equip siteRef:@a-0000 water --- id:@a-0744 dis:Alpha Utility Bills Water Meter 4 Cost custom:{cost} equipRef:@a-0743 his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"\$" --- id:@a-0745 dis:Alpha Utility Bills Water Meter 4 Volume domestic equipRef:@a-0743 his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:gal volume water --- id:@a-0746 dis:Alpha Utility Bills Water Meter 5 equip siteRef:@a-0000 water --- id:@a-0747 dis:Alpha Utility Bills Water Meter 5 Cost custom:{cost} equipRef:@a-0746 his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"\$" --- id:@a-0748 dis:Alpha Utility Bills Water Meter 5 Volume domestic equipRef:@a-0746 his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:gal volume water --- id:@a-0749 dis:Alpha Utility Bills Water Meter 6 equip siteRef:@a-0000 water --- id:@a-074a dis:Alpha Utility Bills Water Meter 6 Cost custom:{cost} equipRef:@a-0749 his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"\$" --- id:@a-074b dis:Alpha Utility Bills Water Meter 6 Volume domestic equipRef:@a-0749 his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:gal volume water --- id:@a-074c dis:Alpha Utility Bills Water Meter 7 equip siteRef:@a-0000 water --- id:@a-074d dis:Alpha Utility Bills Water Meter 7 Cost custom:{cost} equipRef:@a-074c his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"\$" --- id:@a-074e dis:Alpha Utility Bills Water Meter 7 Volume domestic equipRef:@a-074c his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:gal volume water --- id:@a-074f dis:Alpha Utility Bills Water Meter 8 equip siteRef:@a-0000 water --- id:@a-0750 dis:Alpha Utility Bills Water Meter 8 Cost custom:{cost} equipRef:@a-074f his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"\$" --- id:@a-0751 dis:Alpha Utility Bills Water Meter 8 Volume domestic equipRef:@a-074f his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:gal volume water --- id:@a-0752 dis:Alpha Waterside B-1 boiler equip equipRef:@a-07da hotWaterRef:@a-07da hvac siteRef:@a-0000 --- id:@a-0753 dis:Alpha Waterside B-1 Command cmd cur custom:{description:"Boiler 1 S/S"} equipRef:@a-0752 his hisMode:cov kind:Bool point run siteRef:@a-0000 tz:Denver --- id:@a-0754 dis:Alpha Waterside B-1 Firing Rate cur custom:{firingRate description:"B-1 Fire Rate"} equipRef:@a-0752 his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0755 dis:Alpha Waterside B-1 Status cur custom:{description:"Boiler 1 Status"} equipRef:@a-0752 his hisMode:cov kind:Bool point run sensor siteRef:@a-0000 tz:Denver --- id:@a-0756 dis:Alpha Waterside B-2 boiler equip equipRef:@a-07da hotWaterRef:@a-07da hvac siteRef:@a-0000 --- id:@a-0757 dis:Alpha Waterside B-2 Command cmd cur custom:{description:"Boiler 2 S/S"} equipRef:@a-0756 his hisMode:cov kind:Bool point run siteRef:@a-0000 tz:Denver --- id:@a-0758 dis:Alpha Waterside B-2 Firing Rate cur custom:{firingRate description:"B-2 Fire Rate"} equipRef:@a-0756 his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0759 dis:Alpha Waterside B-2 Status cur custom:{description:"Boiler 2 Status"} equipRef:@a-0756 his hisMode:cov kind:Bool point run sensor siteRef:@a-0000 tz:Denver --- id:@a-075a dis:Alpha Waterside B-3 boiler equip equipRef:@a-07da hotWaterRef:@a-07da hvac siteRef:@a-0000 --- id:@a-075b dis:Alpha Waterside B-3 Command cmd cur custom:{description:"Boiler 3 S/S"} equipRef:@a-075a his hisMode:cov kind:Bool point run siteRef:@a-0000 tz:Denver --- id:@a-075c dis:Alpha Waterside B-3 Firing Rate cur custom:{firingRate description:"B-3 Fire Rate"} equipRef:@a-075a his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-075d dis:Alpha Waterside B-3 Status cur custom:{description:"Boiler 3 Status"} equipRef:@a-075a his hisMode:cov kind:Bool point run sensor siteRef:@a-0000 tz:Denver --- id:@a-075e dis:Alpha Waterside Boiler Room HW Sys equip equipRef:@a-07da hot hotWaterRef:@a-07da hvac secondaryLoop siteRef:@a-0000 --- id:@a-075f dis:Alpha Waterside Boiler Room HW Sys HW Pump Status cur custom:{description:"HW Pump Status"} equipRef:@a-075e his hisMode:cov kind:Bool point sensor siteRef:@a-0000 tz:Denver --- id:@a-0760 dis:Alpha Waterside Boiler Room HW Sys HW Supply Temp SP cur custom:{description:"HW Supply Temp SP"} equipRef:@a-075e his kind:Number point siteRef:@a-0000 sp tz:Denver unit:fahrenheit --- id:@a-0761 dis:Alpha Waterside Boiler Room HW Sys Hot Water Delta Pressure cur custom:{description:"HW System DP"} delta equipRef:@a-075e his hot kind:Number point pressure secondaryLoop sensor siteRef:@a-0000 tz:Denver unit:psi water --- id:@a-0762 dis:Alpha Waterside Boiler Room HW Sys Hot Water Delta Pressure Setpoint cur custom:{description:"HW Sys DP SP"} delta equipRef:@a-075e his hot kind:Number point pressure secondaryLoop siteRef:@a-0000 sp tz:Denver unit:psi water --- id:@a-0763 dis:Alpha Waterside Boiler Room HW Sys Hot Water Entering Temp cur custom:{description:"HW Supply Temp"} entering equipRef:@a-075e his hot kind:Number point secondaryLoop sensor siteRef:@a-0000 temp tz:Denver unit:°F water --- id:@a-0764 dis:Alpha Waterside Boiler Room HW Sys Hot Water Leaving Temp cur custom:{description:"HW Return Temp"} equipRef:@a-075e his hot kind:Number leaving point secondaryLoop sensor siteRef:@a-0000 temp tz:Denver unit:°F water --- id:@a-0765 dis:Alpha Waterside Boiler Room HW Sys Steam Valve Control Signal cur custom:{description:"Steam Valve Control Signal"} equipRef:@a-075e his kind:Number point siteRef:@a-0000 sp tz:Denver --- id:@a-0766 dis:Alpha Waterside CH-1 chilled chilledWaterRef:@a-07b8 chiller elec equip equipRef:@a-07b8 hvac meter siteRef:@a-0000 water waterCooling --- id:@a-0767 dis:Alpha Waterside CH-1 Chilled Water Entering Temp chilled cur entering equipRef:@a-0766 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F water --- id:@a-0768 dis:"Alpha Waterside CH-1 Chilled Water Flow (CC)" chilled cur equipRef:@a-0766 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"gal/min" water --- id:@a-0769 dis:Alpha Waterside CH-1 Chilled Water Isolation Valve chilled cmd cur custom:{description:"CH-1 Evap ISO Valve"} equipRef:@a-0766 his hisMode:cov kind:Bool point siteRef:@a-0000 tz:Denver valve water --- id:@a-076a dis:Alpha Waterside CH-1 Chilled Water Isolation Valve chilled cur custom:{description:"CH-1 Evap ISO Valve OPEN"} equipRef:@a-0766 his hisMode:cov kind:Bool point sensor siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-076b dis:Alpha Waterside CH-1 Chilled Water Leaving Temp chilled cur equipRef:@a-0766 his kind:Number leaving point sensor siteRef:@a-0000 temp tz:Denver unit:°F water --- id:@a-076c dis:"Alpha Waterside CH-1 Chilled Water Load (CC)" chilled cur equipRef:@a-0766 his kind:Number point power sensor siteRef:@a-0000 tz:Denver unit:tonref water --- id:@a-076d dis:Alpha Waterside CH-1 Chilled Water Temp Setpoint chilled cur equipRef:@a-0766 his kind:Number leaving point siteRef:@a-0000 sp temp tz:Denver unit:°F water --- id:@a-076e dis:Alpha Waterside CH-1 Command cmd cur equipRef:@a-0766 his hisMode:cov kind:Bool point run siteRef:@a-0000 tz:Denver --- id:@a-076f dis:"Alpha Waterside CH-1 Compressor Efficiency (CC)" cur custom:{component compressor} efficiency equipRef:@a-0766 his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0770 dis:Alpha Waterside CH-1 Compressor Frequency Status cur custom:{compressor} equipRef:@a-0766 freq his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:Hz --- id:@a-0771 dis:"Alpha Waterside CH-1 Compressor Refrig Entering Temp (CC)" cur custom:{compressor} entering equipRef:@a-0766 his kind:Number point refrig sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0772 dis:"Alpha Waterside CH-1 Compressor Refrig Leaving Temp (CC)" cur custom:{compressor} equipRef:@a-0766 his kind:Number leaving point refrig sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0773 dis:"Alpha Waterside CH-1 Cond Efficiency (CC)" condenser cur custom:{component} efficiency equipRef:@a-0766 his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0774 dis:"Alpha Waterside CH-1 Cond Refrig Pressure (CC)" condenser cur equipRef:@a-0766 his kind:Number point pressure refrig sensor siteRef:@a-0000 tz:Denver unit:psi --- id:@a-0775 dis:"Alpha Waterside CH-1 Cond Refrig Saturation Temp (CC)" condenser cur custom:{saturation} equipRef:@a-0766 his kind:Number point refrig sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0776 dis:Alpha Waterside CH-1 Cond Water Entering Temp condenser cur custom:{description:"CH-1 Cond Inlet"} entering equipRef:@a-0766 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F water --- id:@a-0777 dis:"Alpha Waterside CH-1 Cond Water Flow (CC)" condenser cur equipRef:@a-0766 flow his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"gal/min" water --- id:@a-0778 dis:Alpha Waterside CH-1 Cond Water Isolation Valve condenser cur custom:{description:"CH-1 Cond ISO Valve OPEN"} equipRef:@a-0766 his hisMode:cov kind:Bool point sensor siteRef:@a-0000 tz:Denver valve water --- id:@a-0779 dis:Alpha Waterside CH-1 Cond Water Isolation Valve cmd condenser cur custom:{description:"CH-1 Cond ISO Valve"} equipRef:@a-0766 his hisMode:cov kind:Bool point siteRef:@a-0000 tz:Denver valve water --- id:@a-077a dis:Alpha Waterside CH-1 Cond Water Leaving Temp condenser cur custom:{description:"CH-1 Cond Outlet"} equipRef:@a-0766 his kind:Number leaving point sensor siteRef:@a-0000 temp tz:Denver unit:°F water --- id:@a-077b dis:"Alpha Waterside CH-1 Efficiency (CC)" cur efficiency equipRef:@a-0766 his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"kW/ton" --- id:@a-077c dis:"Alpha Waterside CH-1 Elec Power (BAS)" cur elec equipRef:@a-0766 his kind:Number point power sensor siteRef:@a-0000 tz:Denver unit:kW --- id:@a-077d dis:"Alpha Waterside CH-1 Evap Efficiency (CC)" cur custom:{component} efficiency equipRef:@a-0766 evaporator his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-077e dis:Alpha Waterside CH-1 Evap Refrig Pressure cur equipRef:@a-0766 evaporator his kind:Number point pressure refrig sensor siteRef:@a-0000 tz:Denver unit:psi --- id:@a-077f dis:"Alpha Waterside CH-1 Evap Refrig Saturation Temp (CC)" cur custom:{saturation} equipRef:@a-0766 evaporator his kind:Number point refrig sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0780 dis:"Alpha Waterside CH-1 Exp Valve Refrig Entering Temp (CC)" cur custom:{expansionValve} entering equipRef:@a-0766 his kind:Number point refrig sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-0781 dis:Alpha Waterside CH-1 Full Load Amp Percentage cur custom:{fla} equipRef:@a-0766 his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0782 dis:Alpha Waterside CH-1 PHASE B MOTOR CURRENT cur current custom:{mag} elec equipRef:@a-0766 his hisMode:sampled kind:Number point sensor siteRef:@a-0000 tz:Denver unit:A --- id:@a-0783 dis:"Alpha Waterside CH-1 Refrig Cycle Efficiency (CC)" cur custom:{component refrigCycle} efficiency equipRef:@a-0766 his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:"%" --- id:@a-0784 dis:"Alpha Waterside CH-1 Refrig Subcool Delta Temp (CC)" cur custom:{subCool} delta equipRef:@a-0766 his kind:Number point refrig sensor siteRef:@a-0000 temp tz:Denver unit:Δ°F --- id:@a-0785 dis:"Alpha Waterside CH-1 Refrig Suction Superheat Delta Temp (CC)" cur custom:{suction superHeat} delta equipRef:@a-0766 his kind:Number point refrig sensor siteRef:@a-0000 temp tz:Denver unit:Δ°F --- id:@a-0786 dis:"Alpha Waterside CH-1 Status (CC)" cur equipRef:@a-0766 his hisMode:cov kind:Bool point run sensor siteRef:@a-0000 tz:Denver --- id:@a-0787 dis:Alpha Waterside CH-2 chilledWaterRef:@a-07b8 chiller elec equip equipRef:@a-07b8 hvac siteRef:@a-0000 waterCooling --- id:@a-0788 dis:Alpha Waterside CH-2 Chilled Water Entering Temp chilled cur entering equipRef:@a-0787 his hisMode:sampled kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F water --- id:@a-0789 dis:Alpha Waterside CH-2 Chilled Water Isolation Valve chilled cur custom:{description:"CH-2 Evap ISO Valve OPEN"} equipRef:@a-0787 his hisMode:cov kind:Bool point sensor siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-078a dis:Alpha Waterside CH-2 Chilled Water Isolation Valve chilled cmd cur custom:{description:"CH-2 Evap ISO Valve"} equipRef:@a-0787 his hisMode:cov kind:Bool point siteRef:@a-0000 tz:Denver valve water --- id:@a-078b dis:Alpha Waterside CH-2 Chilled Water Leaving Temp chilled cur equipRef:@a-0787 his hisMode:sampled kind:Number leaving point sensor siteRef:@a-0000 temp tz:Denver unit:°F water --- id:@a-078c dis:Alpha Waterside CH-2 Chilled Water Temp Setpoint chilled cur equipRef:@a-0787 his hisMode:sampled kind:Number leaving point siteRef:@a-0000 sp temp tz:Denver unit:°F water --- id:@a-078d dis:Alpha Waterside CH-2 Cond Water Entering Temp condenser cur entering equipRef:@a-0787 his hisMode:sampled kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F water --- id:@a-078e dis:Alpha Waterside CH-2 Cond Water Isolation Valve cmd condenser cur custom:{description:"CH-2 Cond ISO Valve"} equipRef:@a-0787 his hisMode:cov kind:Bool point siteRef:@a-0000 tz:Denver valve water --- id:@a-078f dis:Alpha Waterside CH-2 Cond Water Isolation Valve condenser cur custom:{description:"CH-2 Cond ISO Valve OPEN"} equipRef:@a-0787 his hisMode:cov kind:Bool point sensor siteRef:@a-0000 tz:Denver valve water --- id:@a-0790 dis:Alpha Waterside CH-2 Cond Water Leaving Temp condenser cur equipRef:@a-0787 his hisMode:sampled kind:Number leaving point sensor siteRef:@a-0000 temp tz:Denver unit:°F water --- id:@a-0791 dis:"Alpha Waterside CH-2 Status (CC)" cur custom:{description:"CH-2 Status"} equipRef:@a-0787 his hisMode:cov kind:Bool point run sensor siteRef:@a-0000 tz:Denver --- id:@a-0792 dis:Alpha Waterside CH-3 chilledWaterRef:@a-07b8 chiller elec equip equipRef:@a-07b8 hvac siteRef:@a-0000 waterCooling --- id:@a-0793 dis:Alpha Waterside CH-3 Chilled Water Entering Temp chilled cur entering equipRef:@a-0792 his hisMode:sampled kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F water --- id:@a-0794 dis:Alpha Waterside CH-3 Chilled Water Isolation Valve chilled cmd cur custom:{description:"CH-3 Evap ISO Valve"} equipRef:@a-0792 his hisMode:cov kind:Bool point siteRef:@a-0000 tz:Denver valve water --- id:@a-0795 dis:Alpha Waterside CH-3 Chilled Water Isolation Valve chilled cur custom:{description:"CH-3 Evap ISO Valve OPEN"} equipRef:@a-0792 his hisMode:cov kind:Bool point sensor siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-0796 dis:Alpha Waterside CH-3 Chilled Water Leaving Temp chilled cur equipRef:@a-0792 his hisMode:sampled kind:Number leaving point sensor siteRef:@a-0000 temp tz:Denver unit:°F water --- id:@a-0797 dis:Alpha Waterside CH-3 Chilled Water Temp Setpoint chilled cur equipRef:@a-0792 his hisMode:sampled kind:Number leaving point siteRef:@a-0000 sp temp tz:Denver unit:°F water --- id:@a-0798 dis:Alpha Waterside CH-3 Cond Water Entering Temp condenser cur entering equipRef:@a-0792 his hisMode:sampled kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F water --- id:@a-0799 dis:Alpha Waterside CH-3 Cond Water Isolation Valve condenser cur custom:{description:"CH-3 Cond ISO Valve OPEN"} equipRef:@a-0792 his hisMode:cov kind:Bool point sensor siteRef:@a-0000 tz:Denver valve water --- id:@a-079a dis:Alpha Waterside CH-3 Cond Water Isolation Valve cmd condenser cur custom:{description:"CH-3 Cond ISO Valve"} equipRef:@a-0792 his hisMode:cov kind:Bool point siteRef:@a-0000 tz:Denver valve water --- id:@a-079b dis:Alpha Waterside CH-3 Cond Water Leaving Temp condenser cur equipRef:@a-0792 his hisMode:sampled kind:Number leaving point sensor siteRef:@a-0000 temp tz:Denver unit:°F water --- id:@a-079c dis:"Alpha Waterside CH-3 Status (CC)" cur custom:{description:"CH-3 Status"} equipRef:@a-0792 his hisMode:cov kind:Bool point run sensor siteRef:@a-0000 tz:Denver --- id:@a-079d dis:Alpha Waterside CT-1 chilledWaterRef:@a-07b8 coolingTower elec equip equipRef:@a-07b8 hvac meter siteRef:@a-0000 --- id:@a-079e dis:Alpha Waterside CT-1 Elec Power cur elec equipRef:@a-079d his kind:Number point power sensor siteRef:@a-0000 tz:Denver unit:kW --- id:@a-079f dis:Alpha Waterside CT-1 Fan Command cmd cur custom:{description:"CT-1 S/S"} equipRef:@a-079d fan his hisMode:cov kind:Bool point run siteRef:@a-0000 tz:Denver --- id:@a-07a0 dis:Alpha Waterside CT-1 Fan Frequency cur equipRef:@a-079d fan freq his kind:Number point sensor siteRef:@a-0000 tz:Denver unit:Hz --- id:@a-07a1 dis:Alpha Waterside CT-1 Fan Status cur custom:{description:"CT-1 Status"} equipRef:@a-079d fan his hisMode:cov kind:Bool point run sensor siteRef:@a-0000 tz:Denver --- id:@a-07a2 dis:Alpha Waterside CT-1 Isolation Valve condenser cur custom:{description:"CT-1 ISO Valve OPEN"} equipRef:@a-079d his hisMode:cov kind:Bool point sensor siteRef:@a-0000 tz:Denver valve water --- id:@a-07a3 dis:Alpha Waterside CT-1 Isolation Valve cmd condenser cur custom:{description:"CT-1 ISO Valve"} equipRef:@a-079d his hisMode:cov kind:Bool point siteRef:@a-0000 tz:Denver valve water --- id:@a-07a4 dis:Alpha Waterside CT-2 chilledWaterRef:@a-07b8 coolingTower elec equip equipRef:@a-07b8 hvac meter siteRef:@a-0000 --- id:@a-07a5 dis:Alpha Waterside CT-2 Elec Power cur elec equipRef:@a-07a4 his hisMode:sampled kind:Number point power sensor siteRef:@a-0000 tz:Denver unit:kW --- id:@a-07a6 dis:Alpha Waterside CT-2 Fan Command cmd cur custom:{description:"CT-2 S/S"} equipRef:@a-07a4 fan his hisMode:cov kind:Bool point run siteRef:@a-0000 tz:Denver --- id:@a-07a7 dis:Alpha Waterside CT-2 Fan Frequency cur equipRef:@a-07a4 fan freq his hisMode:sampled kind:Number point sensor siteRef:@a-0000 tz:Denver unit:Hz --- id:@a-07a8 dis:Alpha Waterside CT-2 Fan Speed cur custom:{description:"CT-2 Speed Command"} equipRef:@a-07a4 fan his kind:Number point sensor siteRef:@a-0000 speed tz:Denver unit:"%" --- id:@a-07a9 dis:Alpha Waterside CT-2 Fan Status cur custom:{description:"CT-2 Status"} equipRef:@a-07a4 fan his hisMode:cov kind:Bool point run sensor siteRef:@a-0000 tz:Denver --- id:@a-07aa dis:Alpha Waterside CT-2 Isolation Valve condenser cur custom:{description:"CT-2 ISO Valve OPEN"} equipRef:@a-07a4 his hisMode:cov kind:Bool point sensor siteRef:@a-0000 tz:Denver valve water --- id:@a-07ab dis:Alpha Waterside CT-2 Isolation Valve cmd condenser cur custom:{description:"CT-2 ISO Valve"} equipRef:@a-07a4 his hisMode:cov kind:Bool point siteRef:@a-0000 tz:Denver valve water --- id:@a-07ac dis:Alpha Waterside CWP-1 chilledWaterRef:@a-07b8 condenser elec equip equipRef:@a-07b8 hvac meter pump siteRef:@a-0000 --- id:@a-07ad dis:Alpha Waterside CWP-1 Frequency condenser cur equipRef:@a-07ac freq his kind:Number point pump sensor siteRef:@a-0000 tz:Denver unit:Hz --- id:@a-07ae dis:Alpha Waterside CWP-1 Isolation Valve condenser cur custom:{description:"CWP-1 ISO Valve OPEN"} equipRef:@a-07ac his hisMode:cov kind:Bool point sensor siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-07af dis:Alpha Waterside CWP-1 Isolation Valve cmd condenser cur custom:{description:"CWP-1 ISO Valve"} equipRef:@a-07ac his hisMode:cov kind:Bool point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-07b0 dis:Alpha Waterside CWP-1 Power condenser cur elec equipRef:@a-07ac his kind:Number point power pump sensor siteRef:@a-0000 tz:Denver unit:kW --- id:@a-07b1 dis:Alpha Waterside CWP-1 Status condenser cur custom:{description:"CWP-1 Status"} equipRef:@a-07ac his hisMode:cov kind:Bool point pump run sensor siteRef:@a-0000 tz:Denver --- id:@a-07b2 dis:Alpha Waterside CWP-2 chilledWaterRef:@a-07b8 condenser elec equip equipRef:@a-07b8 hvac meter pump siteRef:@a-0000 --- id:@a-07b3 dis:Alpha Waterside CWP-2 Frequency condenser cur equipRef:@a-07b2 freq his kind:Number point pump sensor siteRef:@a-0000 tz:Denver unit:Hz --- id:@a-07b4 dis:Alpha Waterside CWP-2 Isolation Valve cmd condenser cur custom:{description:"CWP-2 ISO Valve"} equipRef:@a-07b2 his hisMode:cov kind:Bool point siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-07b5 dis:Alpha Waterside CWP-2 Isolation Valve condenser cur custom:{description:"CWP-2 ISO Valve OPEN"} equipRef:@a-07b2 his hisMode:cov kind:Bool point sensor siteRef:@a-0000 tz:Denver unit:"%" valve water --- id:@a-07b6 dis:Alpha Waterside CWP-2 Power condenser cur elec equipRef:@a-07b2 his kind:Number point power pump sensor siteRef:@a-0000 tz:Denver unit:kW --- id:@a-07b7 dis:Alpha Waterside CWP-2 Status condenser cur custom:{description:"CWP-2 Status"} equipRef:@a-07b2 his hisMode:cov kind:Bool point pump run sensor siteRef:@a-0000 tz:Denver --- id:@a-07b8 dis:Alpha Waterside Chilled Water Plant chilled elec equip hvac plant siteRef:@a-0000 water --- id:@a-07b9 dis:Alpha Waterside Chilled Water Plant Chilled Water Delta Pressure Setpoint chilled cur custom:{description:"CHW DP SP"} delta equipRef:@a-07b8 his kind:Number point pressure primaryLoop siteRef:@a-0000 sp tz:Denver unit:psi water --- id:@a-07ba dis:Alpha Waterside Chilled Water Plant Cond Water Entering Temp condenser cur custom:{description:"CW Supply Temp"} entering equipRef:@a-07b8 his kind:Number point sensor siteRef:@a-0000 temp tz:Denver unit:°F water --- id:@a-07bb dis:Alpha Waterside Chilled Water Plant Cond Water Entering Temp Setpoint condenser cur custom:{description:"CWS Temp SP"} entering equipRef:@a-07b8 his kind:Number point siteRef:@a-0000 sp temp tz:Denver unit:°F water --- id:@a-07bc dis:Alpha Waterside Chilled Water Plant Cond Water Leaving Temp condenser cur custom:{description:"CW Return Temp"} equipRef:@a-07b8 his kind:Number leaving point sensor siteRef:@a-0000 temp tz:Denver unit:°F water --- id:@a-07bd dis:Alpha Waterside Chilled Water Plant Outside Air Temp air cur custom:{dryBulb description:"OSA Temperature"} equipRef:@a-07b8 his kind:Number outside point sensor siteRef:@a-0000 temp tz:Denver unit:°F --- id:@a-07be dis:Alpha Waterside HHWP-1 custom:{secondaryLoopRef:@a-075e} elec equip equipRef:@a-075e hot hvac meter pump siteRef:@a-0000 --- id:@a-07bf dis:Alpha Waterside HHWP-1 Frequency cur equipRef:@a-07be freq his hot kind:Number point pump secondaryLoop sensor siteRef:@a-0000 tz:Denver unit:Hz --- id:@a-07c0 dis:Alpha Waterside HHWP-1 Power cur elec equipRef:@a-07be his hot kind:Number point power pump secondaryLoop sensor siteRef:@a-0000 tz:Denver unit:kW --- id:@a-07c1 dis:"Alpha Waterside HHWP-1 Secondary Hot Water Pump S/S Command" cmd cur custom:{description:"HHWP-1 S/S"} equipRef:@a-07be his hisMode:cov hot kind:Bool point pump run secondaryLoop siteRef:@a-0000 tz:Denver --- id:@a-07c2 dis:Alpha Waterside HHWP-2 custom:{secondaryLoopRef:@a-075e} elec equip equipRef:@a-075e hot hvac meter pump siteRef:@a-0000 --- id:@a-07c3 dis:Alpha Waterside HHWP-2 Frequency cur equipRef:@a-07c2 freq his hot kind:Number point pump secondaryLoop sensor siteRef:@a-0000 tz:Denver unit:Hz --- id:@a-07c4 dis:Alpha Waterside HHWP-2 Power cur elec equipRef:@a-07c2 his hot kind:Number point power pump secondaryLoop sensor siteRef:@a-0000 tz:Denver unit:kW --- id:@a-07c5 dis:"Alpha Waterside HHWP-2 Secondary Hot Water Pump S/S Command" cmd cur custom:{description:"HHWP-2 S/S"} equipRef:@a-07c2 his hisMode:cov hot kind:Bool point pump run secondaryLoop siteRef:@a-0000 tz:Denver --- id:@a-07c6 dis:Alpha Waterside HHWP-2 Status cur custom:{description:"HHWP-2 Status"} equipRef:@a-07c2 his hisMode:cov hot kind:Bool point pump run secondaryLoop sensor siteRef:@a-0000 tz:Denver --- id:@a-07c7 dis:Alpha Waterside HHWP-3 custom:{secondaryLoopRef:@a-07e5} elec equip equipRef:@a-07e5 hot hvac meter pump siteRef:@a-0000 --- id:@a-07c8 dis:Alpha Waterside HHWP-3 Frequency cur equipRef:@a-07c7 freq his hot kind:Number point pump secondaryLoop sensor siteRef:@a-0000 tz:Denver unit:Hz --- id:@a-07c9 dis:Alpha Waterside HHWP-3 Power cur elec equipRef:@a-07c7 his hot kind:Number point power pump secondaryLoop sensor siteRef:@a-0000 tz:Denver unit:kW --- id:@a-07ca dis:"Alpha Waterside HHWP-3 Secondary Hot Water Pump S/S Command" cmd cur custom:{description:"HHWP-3 S/S"} equipRef:@a-07c7 his hisMode:cov hot kind:Bool point pump run secondaryLoop siteRef:@a-0000 tz:Denver --- id:@a-07cb dis:Alpha Waterside HHWP-3 Status cur custom:{description:"HHWP-3 Status"} equipRef:@a-07c7 his hisMode:cov hot kind:Bool point pump run secondaryLoop sensor siteRef:@a-0000 tz:Denver --- id:@a-07cc dis:Alpha Waterside HHWP-4 custom:{secondaryLoopRef:@a-07e5} elec equip equipRef:@a-07e5 hot hvac meter pump siteRef:@a-0000 --- id:@a-07cd dis:Alpha Waterside HHWP-4 Frequency cur equipRef:@a-07cc freq his hot kind:Number point pump secondaryLoop sensor siteRef:@a-0000 tz:Denver unit:Hz --- id:@a-07ce dis:Alpha Waterside HHWP-4 Power cur elec equipRef:@a-07cc his hot kind:Number point power pump secondaryLoop sensor siteRef:@a-0000 tz:Denver unit:kW --- id:@a-07cf dis:"Alpha Waterside HHWP-4 Secondary Hot Water Pump S/S Command" cmd cur custom:{description:"HHWP-4 S/S"} equipRef:@a-07cc his hisMode:cov hot kind:Bool point pump run secondaryLoop siteRef:@a-0000 tz:Denver --- id:@a-07d0 dis:Alpha Waterside HHWP-4 Status cur custom:{description:"HHWP-4 Status"} equipRef:@a-07cc his hisMode:cov hot kind:Bool point pump run secondaryLoop sensor siteRef:@a-0000 tz:Denver --- id:@a-07d1 dis:Alpha Waterside HX-1 custom:{secondaryLoopRef:@a-07e5} equip equipRef:@a-07e5 heatExchanger hotWaterRef:@a-07da hvac siteRef:@a-0000 --- id:@a-07d2 dis:"Alpha Waterside HX-1 1/3 Steam Valve" cmd cur custom:{description:"HX-1 1/3 Steam Valve Signal"} equipRef:@a-07d1 his kind:Number point siteRef:@a-0000 steam tz:Denver unit:"%" valve --- id:@a-07d3 dis:"Alpha Waterside HX-1 2/3 Steam Valve" cmd cur custom:{description:"HX-1 2/3 Steam Valve Signal"} equipRef:@a-07d1 his kind:Number point siteRef:@a-0000 steam tz:Denver unit:"%" valve --- id:@a-07d4 dis:Alpha Waterside HX-2 custom:{secondaryLoopRef:@a-07e5} equip equipRef:@a-07e5 heatExchanger hotWaterRef:@a-07da hvac siteRef:@a-0000 --- id:@a-07d5 dis:"Alpha Waterside HX-2 1/3 Steam Valve" cmd cur custom:{description:"HX-2 1/3 Steam Valve Signal"} equipRef:@a-07d4 his kind:Number point siteRef:@a-0000 steam tz:Denver unit:"%" valve --- id:@a-07d6 dis:"Alpha Waterside HX-2 2/3 Steam Valve" cmd cur custom:{description:"HX-2 2/3 Steam Valve Signal"} equipRef:@a-07d4 his kind:Number point siteRef:@a-0000 steam tz:Denver unit:"%" valve --- id:@a-07d7 dis:Alpha Waterside HX-3 custom:{secondaryLoopRef:@a-075e} equip equipRef:@a-075e heatExchanger hotWaterRef:@a-07da hvac siteRef:@a-0000 --- id:@a-07d8 dis:"Alpha Waterside HX-3 1/3 Steam Valve" cmd cur custom:{description:"1/3 Steam Valve Signal"} equipRef:@a-07d7 his kind:Number point siteRef:@a-0000 steam tz:Denver unit:"%" valve --- id:@a-07d9 dis:"Alpha Waterside HX-3 2/3 Steam Valve" cmd cur custom:{description:"2/3 Steam Valve Signal"} equipRef:@a-07d7 his kind:Number point siteRef:@a-0000 steam tz:Denver unit:"%" valve --- id:@a-07da dis:Alpha Waterside Hot Water Plant equip hot hvac plant siteRef:@a-0000 water --- id:@a-07db dis:Alpha Waterside Hot Water Plant Steam Leaving Pressure cur custom:{description:"Steam Pressure"} equipRef:@a-07da his kind:Number leaving point pressure primaryLoop sensor siteRef:@a-0000 steam tz:Denver unit:psi --- id:@a-07dc dis:Alpha Waterside Hot Water Plant Steam Leaving Pressure Setpoint cur custom:{description:"Steam SP"} equipRef:@a-07da his kind:Number leaving point pressure primaryLoop siteRef:@a-0000 sp steam tz:Denver unit:psi --- id:@a-07dd dis:Alpha Waterside PCHWP-1A chilled chilledWaterRef:@a-07b8 elec equip equipRef:@a-07b8 hvac pump siteRef:@a-0000 --- id:@a-07de dis:Alpha Waterside PCHWP-1A Frequency chilled cur equipRef:@a-07dd freq his kind:Number point primaryLoop pump sensor siteRef:@a-0000 tz:Denver unit:Hz --- id:@a-07df dis:Alpha Waterside PCHWP-1A Speed chilled cur custom:{description:"PCHWP-1A Speed Command"} equipRef:@a-07dd his kind:Number point primaryLoop pump sensor siteRef:@a-0000 speed tz:Denver unit:"%" --- id:@a-07e0 dis:Alpha Waterside PCHWP-1A Status chilled cur custom:{description:"PCHWP-1A Status"} equipRef:@a-07dd his hisMode:cov kind:Bool point primaryLoop pump run sensor siteRef:@a-0000 tz:Denver --- id:@a-07e1 dis:Alpha Waterside PCHWP-1B chilled chilledWaterRef:@a-07b8 elec equip equipRef:@a-07b8 hvac pump siteRef:@a-0000 --- id:@a-07e2 dis:Alpha Waterside PCHWP-1B Frequency chilled cur equipRef:@a-07e1 freq his kind:Number point primaryLoop pump sensor siteRef:@a-0000 tz:Denver unit:Hz --- id:@a-07e3 dis:Alpha Waterside PCHWP-1B Speed chilled cur custom:{description:"PCHWP-1B Speed Command"} equipRef:@a-07e1 his kind:Number point primaryLoop pump sensor siteRef:@a-0000 speed tz:Denver unit:"%" --- id:@a-07e4 dis:Alpha Waterside PCHWP-1B Status chilled cur custom:{description:"PCHWP-1B Status"} equipRef:@a-07e1 his hisMode:cov kind:Bool point primaryLoop pump run sensor siteRef:@a-0000 tz:Denver --- id:@a-07e5 dis:Alpha Waterside Penthouse HW Sys equip equipRef:@a-07da hot hotWaterRef:@a-07da hvac secondaryLoop siteRef:@a-0000 --- id:@a-07e6 dis:Alpha Waterside Penthouse HW Sys HW Supply Temp SP cur custom:{description:"HW Supply Temp SP"} equipRef:@a-07e5 his kind:Number point siteRef:@a-0000 sp tz:Denver unit:fahrenheit --- id:@a-07e7 dis:Alpha Waterside Penthouse HW Sys Hot Water Delta Pressure cur custom:{description:"2nd Floor HW Pump DP"} delta equipRef:@a-07e5 his hot kind:Number point pressure secondaryLoop sensor siteRef:@a-0000 tz:Denver unit:psi water --- id:@a-07e8 dis:Alpha Waterside Penthouse HW Sys Hot Water Delta Pressure Setpoint cur custom:{description:"HW Sys DP SP"} delta equipRef:@a-07e5 his hot kind:Number point pressure secondaryLoop siteRef:@a-0000 sp tz:Denver unit:psi water --- id:@a-07e9 dis:Alpha Waterside Penthouse HW Sys Hot Water Entering Temp cur custom:{description:"HW Supply Temp"} entering equipRef:@a-07e5 his hot kind:Number point secondaryLoop sensor siteRef:@a-0000 temp tz:Denver unit:°F water --- id:@a-07ea dis:Alpha Waterside Penthouse HW Sys Hot Water Leaving Temp cur custom:{description:"HW Return Temp"} equipRef:@a-07e5 his hot kind:Number leaving point secondaryLoop sensor siteRef:@a-0000 temp tz:Denver unit:°F water --- id:@a-07eb dis:"Hugo, CO" geoCity:Hugo geoCoord:C(39.13,-103.467) geoCountry:US geoState:CO tz:Denver weatherStation --- id:@a-07ec dis:"Hugo, CO Condition" enum:"unknown,clear,partlyCloudy,cloudy,showers,rain,thunderstorms,ice,flurries,snow" his kind:Str point sensor tz:Denver weather weatherCond weatherStationRef:@a-07eb --- id:@a-07ed dis:"Hugo, CO Humidity" air his humidity kind:Number point sensor tz:Denver unit:"%RH" weather weatherStationRef:@a-07eb --- id:@a-07ee dis:"Hugo, CO Sunrise" daytime his kind:Bool point sensor tz:Denver weather weatherStationRef:@a-07eb --- id:@a-07ef dis:"Hugo, CO Temp" air his kind:Number point sensor temp tz:Denver unit:°F weather weatherStationRef:@a-07eb