chiller
| Kind: | Marker |
|---|---|
| Used With: | equip |
Chillers remove heat from a liquid via a vapor compression or an absorption refrigeration cycle.
From: Chillers | Chillers
Chiller equips are marked with the chiller tag. Equip level tags:
equipRefmust reference parentchilledWaterPlantif associated with a plantwaterCooledorairCooledabsorptionor if vapor compression:reciprocal,screw, orcentrifugalcoolingCapacity
Points associated with chiller equip:
Run/Status
Chilled water to/from AHUs
chilledwaterleavingtempsensorchilledwaterleavingtempspchilledwaterleavingflowsensorchilledwaterleavingpressuresensorchilledwaterenteringtempsensorchilledwaterenteringflowsensorchilledwaterenteringpressuresensorchilledwaterdeltatempsensorchilledwaterdeltaflowsensorchilledwaterdeltapressuresensorchilledwatervalveisolationcmd
Condenser water to/from cooling towers
condenserwaterleavingtempsensorcondenserwaterleavingflowsensorcondenserwaterleavingpressuresensorcondenserwaterenteringtempsensorcondenserwaterenteringpressuresensorcondenserwaterenteringflowsensorcondenserwatervalveisolationcmd
Misc Internal
condensercmdcondenserrefrigtempsensorcondenserrefrigpressuresensorevaporatorrefrigtempsensorevaporatorrefrigpressuresensor
Note: not every combination of sp is listed, just most common setpoints. Chillers share the same point modeling conventions as VFDs. Chillers which measure energy should model their points using the same conventions as elec meters or thermal meters.